WL400
Manual Page 67
–
Revision: 10-23-2019
4.
Compressor is Not Running
Possible Reason
Solution
Green Heater and Compressor
Switch button on unit is in the
off position
Turn Green Heater and Compressor Switch on.
I = ON
Compressor Starting Circuit
Turn Green Heater and Compressor Switch off.
O =
OFF.
Remove the compressor cap on side of the
compressor;
Disconnect the black and red terminal connectors;
Inspect the starter and overload relay for any
defects.
Replace components(s) as needed.
Turn Green Heater and Compressor Switch on.
I = ON and
retest compressor operation.