Start-up procedure
•
Fill the mineral tank with water:
Press and hold the extra cycle button for 5 seconds.
Display will indicate step 1, which is the backwash cycle (as shown above). Once the
display indicates step 1, slowly open bypass valve and let water run to the drain for
approximately 5 minutes. This will bleed any air from the system and flush it to the
drain. After approximately 5 minutes, manually index the valve through the remaining
cycles as follows:
•
Push the extra cycle button
once to advance the valve to regen step 2
•
Push the extra cycle button
once to advance the valve to regen step 3
•
Push the extra cycle button
once to advance the valve to regen step 4
At regen step 4, allow the control to automatically complete step 4 (brine refill) and return
to service. This will place the correct amount of water in the brine tank for start-up.
The unit is now pressurized with water and ready for service
. Proceed to setting current
time.
Placing unit into service