2.4. CUSTOMIZING BOILER FEATURES
As your boiler has an advanced electronic card, operation conditions and
certain parameters related with your preferences may be changed by
our Authorised Service. Please consult our authorised service when any
changes requested in below given parameters.
(P07) Power Ramp-Up Time.
When boiler starts, there’s a ramp-up time for reaching requested power
from minimum power and this is set as 10 minutes as default. This value can
be set from 0 to 80 corresponding to 0 - 800 seconds.
(P08) Central Heating Power.
The maximum Central Heating power can be adjusted by this parameter.
(P21) Low temperature region selection.
This parameter should be adjusted as 1 for ground heating or heating
systems operating with low temperature. 0 (zero) value is selected for
radiator systems to operate at high temperatures as standard.
(P24) Child Protection
This feature is disabled as default factory setting (0). Child Protection (key-
lock) is enabled when parameter is adjusted to 1. Keys are locked after 2
minutes following use when the feature is enabled. Key-lock is released
when the MODE button is hold until cycle is completed for getting off the
child protection
For other functions / parameters to customize your boiler, please refer to
the installation & service manual.
Deareation Function
The boiler has to be switched to OFF mode first. It is possible to activate
deaeration function pressing RESET and ”-“ for circle time.
“Air” will be displayed on the screen. Boiler will start the Deareation
function.
During this function pump and 3-way valve are activated/ deactivated in
order to have deaeration of the hydraulic plant.
This function ends pushing again RESET and ”-“ for circle time or at the end
of deaeration time: 12 minutes.
Figure 6
Reset button
and (–) button are pressed.
0019_00.W210419