FoldSmart™ Installation and Maintenance Manual
Revision 1 - MAY 2023
87
PRELIMINARY TESTING
Preliminary Testing
All the control device inputs listed in Table 6 are shown as a single input. The second wire is connected to
a Common Terminal Bus (1 - 8) on the SmartDC Controller board. The Fire Department Open input is an
exception and requires a +24 Volt input as well as activation in the Installer Menu. For convenience a +24V
terminal is located next to the EMERG OPEN terminal. Refer to
“Figure 12. SmartDC Controller Board”
Table 6. SmartDC Controller Board Inputs
Terminal
No�
Input Name
Pre-2016 Models
Wire Connections
Uses
1-8
COM
COM
All user inputs are energized
when connected to
common except Emergency
Open.
Powering sensors and
accessories.
9
Stop *
Stop
Normally Closed (N.C.)
input. Jumper to Common if
not being used.
Line of sight, external stop
button or 3-button station.
10
Open *
Open
Normally Open (N.O.) input.
Not for radio or remote
access controls.
Line of sight, external open
button or 3-button station.
11
Close
Close
N.O. input. Connection for a
close push-button.
Line of sight, external
connection for a close
button or 3-button station.
12
Radio Open ** Remote Open and
Radio Control
N.O. input. For radio/remote
open device. Program to
also Close using SmartDC
Installer Menu. Access RO in
the User Menu and set to 1.
Remote access controls or
radio controls.
13
Partial Open
Partial Open
Not used in FoldSmart
operators.
N/A
14
Sensor 2
Eye Open
N.C. input. Connection for
Photo Eye Open direction.
Type of sensor used is
programmable in Installer
Menu (S2).
External Entrapment Sensor
15
Sensor 3
Eye Close
N.C. input. Connection for
Photo Eye Close direction.
Type of sensor used is
programmable in Installer
Menu (S3).
External Entrapment Sensor
16
Exit Loop
Free Exit Vehicle
Detector
N.O. input. Connection for
free exit vehicle detector.
Free Exit Vehicle Detector
Содержание FOLDSMART
Страница 35: ...FoldSmart Installation and Maintenance Manual Revision 1 MAY 2023 35 FOLDSMART GATE INSTALLATION ...
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Страница 37: ...FoldSmart Installation and Maintenance Manual Revision 1 MAY 2023 37 FOLDSMART GATE INSTALLATION ...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 FOLDSMART GATE INSTALLATION ...
Страница 146: ......
Страница 147: ...FoldSmart XT Drawings Generic Site Layout and Options ...
Страница 148: ......
Страница 149: ......
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 157: ......
Страница 158: ......
Страница 160: ......
Страница 162: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com ...