Status
This menu reports the status of the input. Possible messages are Normal, High Alarm, Low Alarm, or
Total Limit.
Custom Units
Select the units of measure that you want to use. Type the name in the text box.
One Count =
This menu allows you to specify that each count (contact closure) signifies a certain number of the
custom units of measure. For example, one count could equal 100 liters of fluid.
Total Alarm Limit
You may specify a total number of counts accumulated above which an alarm message will occur. Type
this in the text box. You must go to the Alarm page to specify that this alarm condition is a critical
alarm in order to close the alarm relay or send an email.
Rate High Alarm
You may specify a contact rate above which an alarm message will occur. Type this in the text box.
You must go to the Alarm page to specify that this alarm condition is a critical alarm in order to close
the alarm relay or send an email.
Rate Low Alarm
You may specify a contact rate below which an alarm message will occur. Type this in the text box.
You must go to the Alarm page to specify that this alarm condition is a critical alarm in order to close
the alarm relay or send an email.
Rate Units
Use the pull-down to specify the units of measure for the rate. The choices are pulses per second,
minute, hour, day, week, month, or year.
Digital Input Assignment
Click on the radio button that best describes the devices that you have connected to the digital inputs for
each input labeled 1 through 6. Make sure that you select the type of device that is actually wired to that
terminal of the card!
Not Used
should be selected if nothing is attached to that input.
Paddlewheel Flow meter
should be selected if a high frequency (greater than 10 Hz) Hall Effect
paddlewheel flow meter is connected to that input. This option will give you the ability to specify a K
Factor to convert contact closures into a flow rate.
Contact Flow meter
should be selected if a low frequency (less than 10 Hz) Hall Effect or reed switch
style water meter contactor is connected to that input. This option will give you the ability to specify the
volume of water that will give a contact (generally in multiple gallons or liters per contact).
Generic Input
should be selected if the digital input state (open or closed) will indicate an alarm
condition or if the input state needs to be logged. The WebAlert allows you to specify a custom
message to be delivered if the contact is open or closed.
Generic Counter
should be selected if you need to keep track of the rate of contact closures, or the
total number of contact closures.
Содержание WebAlert WA500
Страница 9: ...6 Figure 1 Identification of Parts...
Страница 10: ...7 Figure 2 Wiring Diagram for AC Power Input...
Страница 11: ...8 Figure 3 Wiring Diagram for Digital Inputs and Outputs...
Страница 12: ...9 Figure 4 Wiring Diagram for Analog Inputs DEVICES POWERED BY THE WEBALERT...
Страница 13: ...10 Figure 5 Wiring Diagram for USB Devices and Communications...
Страница 14: ...11 4 0 FUNCTION OVERVIEW 4 1 Front Panel Alarm LED Status LED...