20
5.2
Startup
Select the option that you want for each of the sections on the page. When you click on the “Submit”
button at the bottom of the page, your changes will take effect. If you move to another page without
clicking “Submit” first, your changes will be lost!
Custom Name
Type the name that you want to use to identify the unit, up to 32 characters, in the text box. For
example, “XYZ Corp, North Tower”.
Time & Date
Update the date and time by typing in the desired values and clicking the arrow on the AM/PM pull-
down list and selecting the correct value.
Site Location
Type the location of the process monitor in the text box.
Date Format
Click on the radio button that corresponds to the desired date format. The choices are Month/Day/Year,
Day/Month/Year or Year/Month/Day.
Digital Input Assignment
Click on the radio button that best describes the devices that you have connected to the digital inputs for
each input labeled 1 through 2. Make sure that you select the type of device that is actually wired to that
terminal of the card!
Not Used
should be selected if nothing is attached to that input.
Contacting Flow Meter
should be selected if a low frequency (10 Hz maximum) contacting-head
water meter is connected to that input. These are generally reed switch sensors that give one dry contact
closure every gallon or more of volume through the meter. . A sensor of this type must be connected to
Digital Input 1-4.
Paddlewheel Flow meter
should be selected if a high frequency (greater than 10 Hz) Hall Effect
paddlewheel flow meter is connected to that input. This option will give you the ability to specify a K
Factor to convert contact closures into a flow rate. A sensor of this type must be connected to Digital
Input 1-4.
Generic Input
should be selected if the digital input state (open or closed) will indicate an alarm
condition or if the input state needs to be logged. The WebAlert allows you to specify a custom
message to be delivered if the contact is open or closed. A sensor of this type can be connected to any
Digital Input.
Generic Counter
should be selected if the contact closure from the sensor will be used to log counts
and/or to initiate a relay to activate for a given time after a given number of counts. . A sensor of this
type must be connected to Digital Input 1-4.
Содержание WebAlert WA500
Страница 9: ...6 Figure 1 Identification of Parts...
Страница 10: ...7 Figure 2 Wiring Diagram for AC Power Input...
Страница 11: ...8 Figure 3 Wiring Diagram for Digital Inputs and Outputs...
Страница 12: ...9 Figure 4 Wiring Diagram for Analog Inputs DEVICES POWERED BY THE WEBALERT...
Страница 13: ...10 Figure 5 Wiring Diagram for USB Devices and Communications...
Страница 14: ...11 4 0 FUNCTION OVERVIEW 4 1 Front Panel Alarm LED Status LED...