Data exchange module 750-654
:$*2
Ç
,
2
Ç
6<67(0
5
Structure of the in- and output data for CanOpen (from firmware WI)
The module is in the list with Index 0x2400 (input) and Index 0x2500 (output). The
module has 2 subindexes.
2 Byte special modules, Inputs
Idx
SIdx
Name
Type
Attrib. Default
Description
2400
0
special 2 byte input
Unsigned8
ro
none
number of 2 Byte channels
....
....
....
....
....
....
n
Input byte0, Input
byte1
Unsigned16
ro
none, 0x0
for WD
error
1. and 2. Input byte
n+1
Input byte2, Input
byte3
Unsigned16
ro
none, 0x0
for WD
error
3. and 4. Input byte
....
....
....
....
....
....
0xFF
0xFF. Special input Unsigned16
ro
none
255. Input channel
2 Byte special modules, Outputs
Idx
SIdx
Name
Type
Attrib. Default
Description
2500
0
special 2 byte
output
Unsigned8
ro
none
number of 2 Byte channels
....
....
....
....
....
....
n
Output byte0,
Output byte1
Unsigned16
rw
none
1. and 2. Output byte
n+1
Output byte2,
Output byte3
Unsigned16
rw
none
3. and 4. Output byte
....
....
....
....
....
....
0xFF
0xFF. special
output
Unsigned16
rw
none
255. Outputkanal
Attention:
The control byte allows the changing of the registers of the module. It must always be 0
in order to avoid a change in the registers. A wrong mapping can change the function of
the module!