Table 27: Register 32
Register 32 - Mode setting
Function
Data type Access
Factory setting
Mode setting
Flags
R/W
0x0020
Bit 0: enUserScaling
0: * User scaling deactivated; the transformation ratio is 1:1.
1:
User scaling activated; the transformation ratio is 1: (divisor for the current
transformer ratio).
Bit 1: reserved
Bit 2: disWdTimer
0: * Watchdog timer activated: The watchdog trips and deactivates the green status LED
“A” if no process data is received within 100 ms.
1:
Watchdog timer not activated.
Bit 3: enFlexProcImage
0: * Simple process image (compatibility mode)
1:
Flexible process image
Bit 4: skipDCFilter
0: * DC filter activated
1:
DC filter is bypassed
Bit 5: reserved
Bit 6: invEnergySign
0: * Energy consumption measurement not inverted.
1:
Energy consumption measurement inverted (generating operation)
Bit 7: enClrMinMaxValues
0: * Automatic deleting of minimum and maximum current, voltage and power values
deactivated.
1:
Automatic deleting of minimum and maximum current, voltage and power values
activated.
Bit 8 … 15: reserved
* Factory setting
Table 28: Register 35
Register 35 - Scaling factor for measuring energy
Function
Data type Access
Factory setting
Scaling factor for measuring energy
UINT
R/W
0x0004
750-493
750-493/000-001
0:
1 mWh
5 mWh
1:
0.01 Wh
0.05 Wh
2:
0.1 Wh
0.5 Wh
3:
1 Wh
5 Wh
4: * 0.01 kWh
0.05 kWh
5:
0.1 kWh
0.5 kWh
6:
1 kWh
5 kWh
≥7:
reserved
reserved
* Factory setting
Table 29: Register 36
Register 36 - Undervoltage threshold
Function
Data type Access
Factory setting
Undervoltage threshold;
resolution 0.1 V
UINT
R/W
0x0064 (10 V)