WAGO-I/O-SYSTEM 750
Device Description
21
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 44 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Pos: 45 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Gerätebeschreibung/Technische Daten - Ü berschrift 2 @ 3\mod_1232967587687_21.docx @ 26924 @ 2 @ 1
3.6
Technical Data
Pos: 46.1 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/T echnische Daten/Anal ogeing angskl emmen/T echnische D aten 750-0493 @ 13\mod_1348667756744_21.docx @ 103558 @ 33333 @ 1
3.6.1
Dimensions and Weight
Table 7: Technical
Data ‒ D
imensions and Weight
Width
12 mm
Height (from upper edge of carrier rail) 64 mm
Length
100 mm
Weight
48 g
3.6.2
Voltage Supply
Table 8: Technical Data
‒ V
oltage Supply
Voltage
System voltage DC 5 V
(via internal bus)
Current consumption
100 mA
Category of overvoltage
III
Rated voltage impulse
4 kV
Degree of distortion
2
3.6.3
Measuring Inputs
Table 9: Technical Data
‒ Measuring I
nputs
Number of inputs
6 (3 voltage inputs, 3 current inputs)
Rated measuring voltage max.
Input resistance typ.
Phase-to-phase voltage Lx - Ly:
480 VAC
Phase voltage Lx - N: 277 VAC/DC
1072 k
Ω
Measuring current max.
1 A for 750-493,
5 A for 750-493/000-001
1 A for 750-493,025-000
5 A for 750-493/025-001
Input resistance typ.
22
mΩ for 750
-493,
5
mΩ for 750
-493/000-001
22 m
Ω
for 750-493/025-000
5 mΩ for 750
-493/025-001
Frequency range
- DC filter activated
- DC filter deactivated
10 … 2000 Hz
0 … 2000 Hz
Max. frequency
7.2 kHz
Signal form
any (in consideration of the frequency
range and max. frequency)