WAGO-I/O-SYSTEM 750
Process Image
29
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
4.4
Control and Status Bytes
Table 17: Control Byte C0
Control Byte C0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg_Com Reserved
Channel_ID
ProcDat_ID
ProcDat_
ID
Here, enter the process data index for the physical variable you wish to read out
using input data word 1.
0:
Current (rms)
1:
Voltage (rms)
2:
Active power
3:
Power factor
4:
Active energy
5:
Max. current
6:
Max. voltage
7:
Max. active power
8:
Frequency
9:
Min. current
10:
Min. voltage
11:
Min. active power
12 .... 15: Reserved
Channel_
ID
Simple
process
image
Always 0
(With the simple process image the channel index has no significance.)
Flexible
process
image
Here, enter the channel index for the channel from which you wish to
read out a measured value using input data word 1.
0: Channel 1
1: Channel 2
2: Channel 3
3: Calibration mode active
Reg_Com 0:
Process data communication
1:
Register communication