8.3
Example: Connecting to Another WSA
Proceed as described below to automatically connect 2 WSAs with one another:
1.
Switch the WSA to operating mode III AutoConnect by interrupting the
power supply two times within the defined time frame (see section
“Switching of Operating Mode by Interrupting the Power Supply”).
2.
Now, switch the second WSA to operating mode III AutoConnect, likewise
by interrupting its power supply two times within the defined time frame.
3.
Wait until both devices have a permanently lit, blue LED.
The two WSAs are now linked to one another.
The link set up in this manner will be restored automatically after an interruption.
You can use AT commands to configure the time within which a reconnect is
carried out after a disruption (see section “Reference AT Commands”> … >“AT
CON RETRY”).
RS-232 interface parameters remain unaffected by this!
A link using AutoConnect applies only to the radio interface and has no impact on
the RS-232 interface parameters.
Baud rate, parity, stop bits and hardware flow control all remain unaffected and
unchanged. If the WSA is still using its factory default settings, for example, these
RS-232 interface parameters are still valid. If the RS-232 devices to be linked
require different RS-232 interface parameters, modify the WSA configuration
accordingly using the AT command interface. You can make these changes either
prior to or after AutoConnect.