WAGO-I/O-SYSTEM 750 XTR
Connect Devices
35
750-xxxx/0040-xxxx Design Notes /XTR
Manual
Version 1.2.0
Pos: 32 /Serie 750 ( WAGO-I/O-SYST EM)/Anschli eßen/Leiter an Push-in CAGE CLAMP® anschließ en - Ü berschrift 2 und T ext @ 6\mod_1258964749000_21.docx @ 44640 @ 2 @ 1
6.4
Connecting a Conductor to the Push-in CAGE
CLAMP
®
The Push-in CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each Push-in CAGE CLAMP
®
connection!
Only one conductor may be connected to each Push-in CAGE CLAMP
®
connection.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Terminate both solid and stranded or ferruled conductors by simply pushing them
in - no tool required. For all other types of conductors, Push-in CAGE CLAMP
®
must be opened for connection with an operating tool with a 2.5 mm blade (order
no. 210-719).
1.
To open the Push-in CAGE CLAMP
®
insert the actuating tool into the
opening above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
To close the Push-in CAGE CLAMP
®
simply remove the tool - the
conductor is then clamped firmly in place.
Figure 12: Connecting a Conductor to a Push-in CAGE CLAMP
®
Pos: 33 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1