WAGO-I/O-SYSTEM 750 XTR
Assembly
29
750-xxxx/0040-xxxx Design Notes /XTR
Manual
Version 1.2.0
Pos: 26.15 /Serie 750 ( WAGO-I/O-SYST EM)/Monti eren/D emonti eren/Ger äte ei nfügen und entfernen - Ü berschrift 2 @ 3\mod_1231768483250_21.docx @ 25950 @ 2 @ 1
5.6
Inserting and Removing Devices
Pos: 26.16 /Alle Serien (Allgemeine M odul e)/Sicherheits- und sonstige Hinweise/Achtung/Achtung: Arbeiten an Geräten nur spannungsfrei durchführen! @ 6\mod_1256193963573_21.docx @ 43426 @ @ 1
Perform work on devices only if they are de-energized!
Working on energized devices can damage them. Therefore, turn off the power
supply before working on the devices.
Pos: 26.17 /Serie 750 ( WAGO-I/O-SYST EM)/Monti eren/D emonti eren/F eldbuskoppler/-controll er ei nfügen @ 3\mod_1234168173031_21.docx @ 27456 @ 3 @ 1
5.6.1
Inserting the Fieldbus Coupler/Controller
1.
When replacing the fieldbus coupler/controller for an already available
fieldbus coupler/controller, position the new fieldbus coupler/controller so
that the tongue and groove joints to the subsequent I/O module are engaged.
2.
Snap the fieldbus coupler/controller onto the carrier rail.
3.
Use a screwdriver blade to turn the locking disc until the nose of the locking
disc engages behind the carrier rail (see the following figure). This prevents
the fieldbus coupler/controller from canting on the carrier rail.
With the fieldbus coupler/controller snapped in place, the electrical connections
for the data contacts and power contacts (if any) to the possible subsequent I/O
module are established.
Pos: 26.18 /Serie 750 ( WAGO-I/O-SYST EM)/Monti eren/D emonti eren/Verrieg elung - Bil d (Standar d) @ 3\mod_1231768944875_21.docx @ 25953 @ @ 1
Figure 5: Release Tab Standard Fieldbus Coupler/Controller (Example)
Pos: 26.19 /Serie 750 ( WAGO-I/O-SYST EM)/Monti eren/D emonti eren/F eldbuskoppler/-controll er entfer nen @ 4\mod_1239169358453_21.docx @ 30330 @ 3 @ 1
5.6.2
Removing the Fieldbus Coupler/Controller
1.
Use a screwdriver blade to turn the locking disc until the nose of the locking
disc no longer engages behind the carrier rail.
2.
Remove the fieldbus coupler/controller from the assembly by pulling the
release tab.
Electrical connections for data or power contacts to adjacent I/O modules are
disconnected when removing the fieldbus coupler/controller.
Pos: 26.20 /Serie 750 ( WAGO-I/O-SYST EM)/Monti eren/D emonti eren/Buskl emme einfügen @ 3\mod_1231769726703_21.docx @ 25989 @ 3 @ 1