WAGO-I/O-SYSTEM 750
Commissioning 79
750-564 4AO U/I
Manual
Version 1.0.0
Table 60: Specific Module/Channel Parameters – PROFINET IO Couplers
GSD File
WAGO-I/O-
CHECK
Name
Value
Selection field
Value
Diagnosis: short circuit
[Channel x (x = 0…3)]
0 (false)
Diagnosis: Short circuit
[Channel x (x = 1…4)]
Off
1 (true)
*)
On
*)
Diagnosis: wire break
[Channel x (x = 0…3)]
0 (false)
Diagnosis: Wire break
[Channel x (x = 1…4)]
Off
1 (true)
*)
On
*)
Diagnostics:
Wiring error
[Channel x (x = 0…3)]
0 (false)
Diagnosis: Wiring error
[Channel x (x = 1…4)]
Off
1 (true)
*)
On
*)
Diagnostics:
Internal error
[Channel x (x = 0…3)]
0 (false)
Diagnosis: Internal error
[Channel x (x = 1…4)]
Off
1 (true)
*)
On
*)
User scaling
[Channel x (x = 0…3)]
deactivated
*)
User scaling
[Channel x (x = 1…4)]
Box unchecked
*)
activated
Box checked
Offset
[Channel x (x = 0…3)]
−
32768 … 0
*)
… 32767 Offset
[Channel x (x = 1…4)]
−
32768 … 0
*)
…
32767
Gain
[Channel x (x = 0…3)]
−
32768 … 16384
*)
…
32767
Gain
[Channel x (x = 1…4)]
−
2.0000 … 1.0000
*)
… 1.9999
3)
Response to K-Bus
timeout
[Channel x (x = 0…3)]
deactivated
Behaviour on K-Bus
timeout
[Channel x (x = 1…4)]
Deactivated
hold last output value
Hold last output
value
set output to high
impedance
*)
Set output high-
impedance
*)
output user substitute
value
Set output to user
substitute value
User substitute value
[Channel x (x = 0…3)]
0
*)
… 65535
1)
−
32768 … 0
*)
…
32767
2)
User substitute value
[Channel x (x = 1…4)]
0x0000
*)
… 0xFFFF
1)
0x8000 … 0x0000
*)
… 0x7FFF
2)
*)
Factory setting
1)
16-bit resolution
2)
15-bit resolution
3)
The resolution of 1/16384 is already taken into account in WAGO-I/O-
CHECK
.
=== Ende der Liste für Textmarke Inhalt_mitte ===
Table 61: PROFIenergy Parameters
3)
– PROFINET IO Couplers
GSD File
WAGO-I/O-
CHECK
Name
Value
Selection field
Value
Minimum pause time
[I/O module]
infinite
*)
n/a
n/a
10 s
1 min
10 min
1 h
10 h
1 d
Pause output value
[Channel x (x =
0…3)]
0
*)
… 65535
1)
−
32768 … 0
*)
… 32767
2)
n/a
n/a
*)
Factory setting
1)
16-bit resolution
2)
15-bit resolution
3)
You can find further explanations in the manuals for the PROFINET fieldbus couplers/
controllers.