42 Process Image
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Manual
Version 1.0.0
Table 39: 0-20 mA (15-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
0 mA
0x0000
0
1 mA
0x0666
1638
2 mA
0x0CCD
3277
3 mA
0x1333
4915
4 mA
0x1999
6553
5 mA
0x2000
8192
6 mA
0x2666
9830
7 mA
0x2CCC
11468
8 mA
0x3333
13107
9 mA
0x3999
14715
10 mA
0x4000
16384
11 mA
0x4666
18022
12 mA
0x4CCC
19660
13 mA
0x5333
21299
14 mA
0x5999
22937
15 mA
0x5FFF
24575
16 mA
0x6666
26214
17 mA
0x6CCC
27852
18 mA
0x7332
29490
19 mA
0x7999
31129
20 mA
0x7FFF
32768
Table 40: 4-20 mA (16-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
4 mA
0x0000
0
5 mA
0x1000
4096
6 mA
0x2000
8192
7 mA
0x3000
12288
8 mA
0x4000
16384
9 mA
0x5000
20480
10 mA
0x6000
24576
11 mA
0x7000
28672
12 mA
0x8000
32768
13 mA
0x8FFF
36863
14 mA
0x9FFF
40959
15 mA
0xAFFF
45055
16 mA
0xBFFF
49151
17 mA
0xCFFF
53247
18 mA
0xDFFF
57343
19 mA
0xEFFF
61439
20 mA
0xFFFF
65535