WAGO-I/O-SYSTEM 750
Process Image 39
750-564 4AO U/I
Manual
Version 1.0.0
4.3.3
Process Values (Current)
Table 33: 0-10 mA (16-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
0 mA
0x0000
0
1 mA
0x199A
6554
2 mA
0x3333
13107
3 mA
0x4CCD
19661
4 mA
0x6666
26214
5 mA
0x8000
32768
6 mA
0x9999
39321
7 mA
0xB333
45875
8 mA
0xCCCC
52428
9 mA
0xE666
58982
10 mA
0xFFFF
65535
Table 34: 0-10 mA (15-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
0 mA
0x0000
0
1 mA
0x0CCD
3277
2 mA
0x1999
6553
3 mA
0x2666
9830
4 mA
0x3333
13107
5 mA
0x4000
16384
6 mA
0x4CCC
19660
7 mA
0x5999
22937
8 mA
0x6666
26214
9 mA
0x7332
29490
10 mA
0x7FFF
32767
Table 35: 2-10 mA (16-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
2 mA
0x0000
0
3 mA
0x2000
8192
4 mA
0x4000
16384
5 mA
0x6000
24576
6 mA
0x8000
32768
7 mA
0x9FFF
40959
8 mA
0xBFFF
49151
9 mA
0xDFFF
57343
10 mA
0xFFFF
65535