48 Process Image
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Manual
Version 1.0.0
Table 45: ±20 mA
Current Value (
I
)
Process Value (hex)
Process Value (dec)
+20 mA
0x745C
29788
+21 mA
0x7A2E
31278
+22 mA
0x7FFF
32767
Table 46: 0-12 mA (16-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
0 mA
0x0000
0
1 mA
0x1555
5461
2 mA
0x2AAB
10923
3 mA
0x4000
16384
4 mA
0x5555
21845
5 mA
0x6AAA
27306
6 mA
0x8000
32768
7 mA
0x9555
38229
8 mA
0xAAAA
43690
9 mA
0xBFFF
49151
10 mA
0xD555
54613
11 mA
0xEAAA
60074
12 mA
0xFFFF
65535
Table 47: 0-12 mA (15-Bit Resolution)
Current Value (
I
)
Process Value (hex)
Process Value (dec)
0 mA
0x0000
0
1 mA
0x0AAB
2731
2 mA
0x1555
5461
3 mA
0x2000
8192
4 mA
0x2AAA
10922
5 mA
0x3555
13653
6 mA
0x4000
16384
7 mA
0x4AAA
19114
8 mA
0x5555
21845
9 mA
0x5FFF
24575
10 mA
0x6AAA
27306
11 mA
0x7554
30036
12 mA
0x7FFF
32767