WAGO-I/O-SYSTEM 750
Commissioning 73
750-564 4AO U/I
Manual
Version 1.0.0
Table 54: “Calibration” Menu Item for Each Channel
Parameter
Value
Description
Manufacturer
calibration
Offset
[Display field]
Indicates the offset value setting.
Gain
[Display field]
Indicates the gain value setting.
User calibration
*)
User calibration is deactivated.
User calibration is activated.
By enabling this setting, you can also specify
the individual gain and offset values.
Offset
[Input Field]
The offset value causes a zero offset of the
process value (shift along the Y axis).
The value entered must fall within the value
range
−32768
… 32767.
Gain
[Input field]
The gain value is used as a gain factor applied
to the process value.
The value entered must fall within the range
from −2.0000 to 1.9999.
The resolution of 1/16384 has already been
taken into account for the decimal entry.
Process value
[Input field]
The process value (current/voltage value) for
the selected channel can be entered in this
input field.
Note:
Confirm the input with the “Return” key on
your keyboard to write the process value to the
I/O module!
Show values in
hexadecimal
Hexadecimal representation is enabled.
*
Hexadecimal representation is disabled.
*)
Factory setting
7.2
Configuration and Parameterization with
e!COCKPIT
4
The
750-564
I/O module is supported by the
e!
COCKPIT
commissioning tool
starting with version 1.6.1.4 – see manual “2759-0101
e!
COCKPIT
,” Section
“Operating.”