68 Commissioning
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Manual
Version 1.0.0
Table 52: Menu Items “Channel 1” ... “Channel 4”
Parameter
Value
Description
Resolution
1)
15 Bit
With resolution “15 Bit,” 15 bits are
provided for the output range.
Example:
With a measurement range
setting of “0–10 V,”
0x0000 = 0 V and 0x7FFF = 10 V.
Values from 0x8000 to 0xFFFF are
ignored in this setting or always provide
the lower endpoint of the range (i.e.: 0 V,
0 mA, 2 V, 2 mA etc.).
16 Bit
*)
With resolution “16 Bit,” the entire
numerical range is provided for the output
value.
Example:
With a measurement range
setting of “0–10 V,”
0x0000 = 0 V and 0xFFFF = 10 V.
Channel
diagnosis
Off
Switches diagnostics on/off for the
channel in general. Switching off channel
diagnostics causes the settings for the
individual diagnostics “wire break,” “short
circuit” etc. to be ignored. The status byte
then also always remains at 0x00 when
there is a pending diagnosis.
Note:
If channel diagnostics are switched
off for this channel, the global diagnostic
settings (see “Common” menu item) are
ignored for this channel!
On
*)
Diagnosis:
Wire break
2)
Off
Switches wire break diagnosis on/off
On
*)
Diagnosis:
Short circuit
3)
Off
Switches short circuit diagnosis on/off
On
*)
Diagnosis:
Wiring error
Off
Switches wiring error diagnosis on/off
On
*)
Diagnosis:
Internal error
Off
Switches internal error diagnosis on/off
On
*)