Use in Hazardous Environments
WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms /XTR
Manual
Version 1.2.0
Pos: 63.16 /Serie 750 ( WAGO-I/O-SYST EM)/Ei nsatz i n Ex-Bereichen/Besonder e Beding ung en für den sicher en Ex- Betrieb gem. AT EX-Z ertifi kat TÜV 14 ATEX 148929_X @ 21\mod_1416995371807_21.docx @ 169118 @ 3 @ 1
7.2.1
Special Conditions for Safe Use (TÜV 14 ATEX 148929 X)
1.
The modules of the WAGO-I/O-SYSTEM 750-*** have to been erected in
such a way, that corresponding to EN 60079-15 a degree of protection of at
least IP 54 according to EN 60529 is achieved.
2.
Measures have to been taken, external to the modules, to provide a transient
protection that ensures that the rated voltage, connected to the power supply
terminals, is not exceeded by more than 40 %
.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted if no explosive atmosphere exists. This although applies for
the all switches, interfaces (Fieldbus, Ethernet, Serial) and the SD-card.
4.
T
he ambient temperature range is: 0 °C ≤ T
amb
≤ +60 °C
The ambient temperature range for modules with suffix extension /025-****
is: -20
°C ≤ T
amb
≤ +60 °C