14
Device Description
WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms /XTR
Manual
Version 1.2.0
Do not exceed maximum current via power contacts!
The maximum current to flow through the power jumper contacts is temperature
dependent:
•
Up to 60 °C: 10 A
•
From 60 °C: 8 A
Greater currents can damage the power contacts. When configuring the system,
do not exceed this current. If that is the case, you must use an additional supply
module.
Pos: 18.11 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hinweise/Hinweis/Hi nweis: XTR - M ax. Busklemmenanzahl beachten! @ 16\mod_1372412268785_21.docx @ 125110 @ @ 1
Observe the maximum number of I/O modules when using the ground
connection!
When using the ground CAGE CLAMP
®
connection, the field power must be
reapplied after every seven 750-407/040-000 I/O modules!
Pos: 18.12 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Gal vanische Trennung F eld/System @ 3\mod_1233756478750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 18.13 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Anordnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.
Pos: 18.14 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hinweise/Hinweis/Hi nweis: XTR - Mischbetri eb XTR /Standard @ 15\mod_1367496420828_21.docx @ 118326 @ @ 1
Mixed operation
Mixed operation (standard/XTR modules) within a node is possible when groups
of modules are electrically isolated on the field side (i.e., electrically isolated
power supply).
Pos: 18.15 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hinweise/Hinweis/Hi nweis: XTR - Erhöhte Störfestig keit @ 15\mod_1367496424993_21.docx @ 118330 @ @ 1
Increased interference!
For standard-compliant application in substation instrumentation and control,
telecontrol systems, railway technology or shipbuilding certified operation,
field-side power supply filter 750-624/040-001 or power supply filter
750-626/040-000 are generally to be used for XTR module groups.
Pos: 18.16 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Einsatzbereich/Einsatzbereich 750- xxxx/040-000 alle XTR-Koppl er/-Controll er ohne Ei nschränkung @ 15\mod_1368425919479_21.docx @ 119444 @ @ 1
The I/O module can be operated with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750 XTR.
Observe the instructions for mixed operation when used in mixed operation
behind standard fieldbus couplers/controllers.
Pos: 19 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1