26
Device Description
WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms /XTR
Manual
Version 1.2.0
Pos: 47.4 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/N ormen und Richtlini en/EM V-Nor men Contr oller 750- xxxx/EM V-Nor men Busklemme 750- xxxx/0040-0000, nur Standar dversi on - Ei nlei tung XTR @ 18\mod_1395909426189_21.docx @ 149708 @ @ 1
The I/O module 750-407/040-000 meets the following EMC standards as these
standards relate to the I/O module:
Pos: 47.5 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/N ormen und Richtlini en/Nor men Störfestig keit XTR @ 18\mod_1394030613258_21.docx @ 147348 @ @ 1
Table 17: EMC – Immunity to Interference
Standard
Test Value
Electrostatic Discharge
• EN
61000-4-2
• EN
60255-22-2
•
IEEE C37.90.3
8 kV (contact discharge)
8 kV (air discharge)
High-frequency Electromagnetic Fields
• EN
61000-4-3 + A1: + A2
• EN
60255-22-3
•
IEEE C37.90.2
20 V/m (80 MHz … 1 GHz)
10 V/m (1 GHz … 3 GHz)
Fast Electrical Transient Disturbances / Burst
• EN
61000-4-4
• EN
60255-22-4
•
IEEE C37.90.1
4 kV
Surge Voltage / Surge
• EN
61000-4-5
• EN
60255-22-5
2 kV (conductor/conductor)
4 kV (conductor/ground)
Conducted Disturbances, Induced by High-frequency Fields
•
EN 61000-4-6
• EN
60255-22-6
10 V (150 kHz … 80 MHz)
Magnetic Fields With Electrical Frequencies
• EN
61000-4-8
300 A/m continuous / 1000 A/m for 1 s
Pulse-shaped magnetic fields
• EN
61000-4-9 + A1
300 A/m
Damped Oscillatory Magnetic Fields
• EN
61000-4-10 + A1
100 A/m
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000
-4-11
Standard not applicable
Damped Sinusoidal Oscillations
• EN 61000
-4-12
2 kV (conductor/conductor)
4 kV (conductor/ground)
Harmonics and Interharmonics
• EN
61000-4-13 + A1
Standard not applicable
Conducted Asymmetric Disturbances
• EN
61000-4-16 + A1 + A2
30 V continuous
300 V for 1 s
Line Frequency Disturbances
• EN
60255-22-7
**)
Class A
(150 V conductor/conductor / 300 V
conductor/ground)
Alternating Components of the Voltage to DC Line Connections
• EN
61000-4-17+A2
15 %