2789-9080
Fieldbus Description
20
| Version: 1.1.0
Communication Module IO-Link
In-
dex
Sub
inde
x
Param-
eter
Access
Data type Data
Storage
Default set-
ting
Range
Data
length
(Bytes)
Description
393 0
Over-
load
warning
thresh-
old
read/write UIntegerT Yes
2.5 A: 0 mA
5 A: 0 mA
10 A: 0 mA
15 A: 0 mA
20 A: 0 mA
40 A: 0 mA
0 … 2500 mA
0 … 5000 mA
0 …10000 mA
0 …15000 mA
0 …20000 mA
0 …40000 mA
2
Overload threshold
between > 0 A and
rated current.
394 0
Output
Behav-
ior
read/write UIntegerT Yes
2
Behavior settings
(for options
see
8
395 0
Switch-
on de-
lay
read/write UIntegerT Yes
0 ms
0 … 60000 ms
2
User-configurable
switch-on delay
(waiting time be-
tween AC mains
voltage is applied,
i.e., the processor
has booted and
power stages are
switched on).
404 0
Trip
current
read/write UIntegerT Yes
2,5 A:
2500 mA
5 A:
5000 mA
10 A:
10000 mA
15 A:
15000 mA
20 A:
20000 mA
40 A:
40000 mA
250 …
2500 mA
500 …
5000 mA
1000 …
10000 mA
1500 …
15000 mA
2000 …
20000 mA
4000 …
40000 mA
2
User-configurable
threshold between
10 % of rated cur-
rent and rated cur-
rent.
405 0
Trip de-
lay
read/write UIntegerT Yes
100 ms
100 …
60000 ms
2
Circuit breaker fun-
tion:
User-configurable
time how long an
overcurrent is ig-
nored.
100 … 60000 ms
424 0
Signali-
sation
Config-
uration
of digi-
tal input
read/write UIntegerT No
2
Digital input be-
havior settings (for
options see
8
432 0
Signali-
sation
Config-
uration
of digi-
tal out-
put
read/write UIntegerT No
2
Digital output be-
havior settings (for
options see
8