2789-9080
Fieldbus Description
| Version: 1.1.0
25
Communication Module IO-Link
Digital input settings
Bits 10 to 12 control the settings of the digital input.
Table 35: Digital input settings
Bit 10
Bit 11
Bit 12
IODD Value
Description
0
0
0
Non-inverted
normal, not inverted
1
0
0
Inverted
inverted
0
1
0
Function triggered by low-high
transition
Function on edge change (0 to 1)
0
0
1
Function triggered by high-low
transition
Function on edge change (1 to 0)
4.2.4.9 Configuration of digital output (Index 432)
DC OK
Bit 0 enables or disables the output of the DC OK status via the digital output.
Table 36: DC OK
Bit 0
IODD Value
Description
1
active
enabled
0
inactive
disabled
Load current warning level exceeded
Bit 1 indicates whether the overload warning threshold has been exceeded.
Table 37: Load current warning level exceeded
Bit 1
IODD Value
Description
1
active
enabled
0
inactive
disabled
Electronic circuit breaker tripped
Bit 2 indicates whether the electronic circuit breaker has tripped.
Table 38: Electronic circuit breaker tripped
Bit 2
IODD Value
Description
1
active
enabled
0
inactive
disabled
Power supply switched off (latched)
Bit 3 controls the latching shutdown.
Table 39: Power supply switched off (latched)
Bit 3
IODD Value
Description
1
active
enabled
0
inactive
disabled
Enable switching DO on/off via process data
Bit 4 enables or disables the control of the output via cyclic process data.