2789-9080
Fieldbus Description
| Version: 1.1.0
23
Communication Module IO-Link
4.2.4.4 Stop bits (Index 383)
Table 24: Selection options for stop bits
Value
IODD Value
Description
0
0
1
1
1
0.5
2
2
2
3
3
1.5
4.2.4.5 Parity (Index 384)
Table 25: Selection options for parity
Value
IODD Value
Description
0
Off
None
1
Even
Even
2
Odd
Odd
4.2.4.6 Data format (Index 386)
Table 26: Selection options for data formats
Value
IODD Value
Description
0
Big endian
B0, B1, B2, B3
1
Middle endian
B2, B3, B0, B1
2
Little endian
B3, B2, B1, B0
4.2.4.7 Output behavior (Index 394)
Output on
Bit 0 enables or disables the output.
Table 27: Output on
Bit 0
IODD Value
Description
1
active
enabled
0
inactive
disabled
“Active Droop” parallel mode
Bit 1 enables or disables the “Active Droop” parallel switching mode.
Table 28: “Active Droop” parallel mode
Bit 1
IODD Value
Description
1
active
enabled
0
inactive
disabled
Overload warning
Bit 2 enables or disables the overload threshold warning.
Table 29: Overload warning
Bit 2
IODD Value
Description
1
active
enabled
0
inactive
disabled