12 - ZTA9648O - User manual
• Avoid the proximity of power groups, especially those with phase control.
• The use of appropriate mains filters on the power supply of the machine in
which the device will be installed is recommended, particularly in the case
of 230VAC power supply.
The device is designed to be assembled to other machines, and therefore
its CE marking does not exempt the plant manufacturer from the safety and
compliance obligations of the machine as a whole.
• To wire terminals 1...6, use crimped tube ferrules or flexible or rigid copper
wire between 0.2 and 2.5 mm² (min. AWG24, max. AWG16; Minimum
temperature rating of wire to be connected to field wiring terminals, 70°C).
The stripping length is 10 mm
• To wire terminals 7...18, use crimped tube ferrules or flexible or rigid copper
wire between 0.2 and 1.5 mm² (min. AWG24, max. AWG16; Minimum
temperature rating of wire to be connected to field wiring terminals, 70°C).
The stripping length is 10 mm.
5.1
Wiring diagram