User manual - ZTA9648O - 37
Disabled
(
Default
)
Hardware input filter is disabled.
Enabled
Hardware input filter limiting the input signal
bandwidth to 1 KHz is enabled
33
Software filter
38
Software filter
Selects digital input software filter.
OFF (
Default
)
No software filter applied to input signal.
0,5..100,0 ms
Software filter applied to input signal cuts any
pulses with a duration shorter than the time set in
the filter.
34
Active status
39
Active status
Selects input signal active state.
Up front (
Default
) Counting action will take place on the input signal
up front
Down front
Counting action will take place on the input signal
down front.
11.3
Digital input 3..4
Parameters for configuring digital input 3 and 4, dedicated to activating
auxiliary functions.
41
Hardware type
46
Hardware type
Select type of digital input hardware.
NPN
Input suitable for sensors with NPN output.
Activation is initiated by short-circuiting the input
to ground (0V)
PNP (
Default
)
Input suitable for sensors with PNP output.
Activation starts by bringing a positive signal
(+12/24 Vdc) to the digital input.