• The value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STOP must be higher than the value
in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_START.
MB AD DR ZONE SCHEDULE SAT WORK 2 ST AR T - - allows to set a date of commencement
of second daily heating period for Saturday. Allowable values for the variable fall within a range from 0 to
1425 (00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error message.
The variable is stored in backed-up EEPROM memory.
MB_ADDR_ZONE_S CHEDULE_SAT_W ORK_2_S TART = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 905(15:05) to
the register will lead to set the value equal to 900 (15:00)
•
The value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_START must be lower than the
value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STOP.
MB AD DR ZON E S C HED ULE S AT WOR K 2 STOP - allows to set a date of end of second
daily heating period for Saturday. Allowable values for the variable fall within a range from 0 to 1425 (00:00
to 23:45). Attempt to record a number beyond the allowable values leads to an error message. The variable is
stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STOP = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 1330 (22:10)
to the register will lead to set the value equal to 1320 (22:00)
•
The value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STOP must be higher than the
value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_START.
MB AD DR ZONE S C HEDULE S UN WOR K 1 ST AR T - allows to set a date of
commencement of first daily heating period for Sunday. Allowable values for the variable fall within a range
from 0 to 1425 (00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error
message. The variable is stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_START = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 532 (08:52) to
the register will lead to set the value equal to 525 (8:45).
•
The value in MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_START must be lower than the
value in MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_STOP.
18