Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 905(15:05) to
the register will lead to set the value equal to 900 (15:00)
•
The value in MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_START must be lower than
the value in
MB ADDR ZONE SCHEDULE MON FRI WORK 2 STOP.
MB AD DR ZONE SCHEDULE MON FRI WORK 2 STOP
Allows to set a date of end of second daily heating period for following days in the schedule: Monday,
Tuesday, Wednesday, Thursday, Friday. Allowable values for the variable fall within a range from 0 to 1425
(00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error message. The
variable is stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_STOP = h * * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 1330 (22:10)
to the register will lead to set the value equal to 1320 (22:00)
•
The value in MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_STOP must be higher than
the value in
MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_START.
MB ADDR ZONE SCHEDULE SAT WORK 1 START - allows to set a date of commencement of
first daily heating period for Saturday. Allowable values for the variable fall within a range from 0 to 1425
(00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error message. The
variable is stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_START = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 532 (08:52)
to the register will lead to set the value equal to 525 (8:45).
• The value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_START must be lower than the
value in MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STOP.
MB ADDR ZONE SCHEDULE SAT WORK 1 STOP - allows to set a date of end of the first daily
heating period for Saturday. Allowable values for the variable fall within a range from 0 to 1425 (00:00 to
23:45). Attempt to record a number beyond the allowable values leads to an error message. The variable is
stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STOP = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 803 (13:23)
to the register will lead to set the value equal to 795 (13:15)