Caution !!!
•
Values recorded in the register are rounded to 0.5[°C].. E.g. sending a number equal to 2254
(22.54[°C]) to the register leads to setting a value of 2250 (22.50[°C]).
•
Should the recorded value of the minimal temperature be lower than currently set target temperature
(MB_ADDR_ZONE_TEMPERATURE_TARGET), the value of target temperature will be
overwritten by the maximal temperature value .
MB AD DR ZONE SCHEDULE MON FRI WORK 1 START
Allows to set a date of commencement of first daily heating period for following days in the schedule:
Monday, Tuesday, Wednesday, Thursday, Friday. Allowable values for the variable fall within a range from
0 to 1425 (00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error
message. The variable is stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_START = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 532(08:52) to
the register will lead to set the value equal to 525 (8:45).
•
Value in MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_START must be lower than the
value in
MB ADDR ZONE SCHEDULE MON FRI WORK 1 STOP.
MB AD DR ZONE SCHEDULE MON FRI WORK 1 STOP
Allows to set a date of end of first daily heating period for following days in the schedule: Monday, Tuesday,
Wednesday, Thursday, Friday. Allowable values for the variable fall within a range from 0 to 1425 (00:00 to
23:45). Attempt to record a number beyond the allowable values leads to an error message. The variable is
stored in backed-up EEPROM memory.
MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_STOP = h * 60 + m.
Caution !!!
•
Values recorded in the register are rounded to 15[min]. E.g. sending a number equal to 803(13:23) to
the register will lead to set the value equal to 795 (13:15)
•
The value in MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_STOP must be higher than
the value in
MB ADDR ZONE SCHEDULE MON FRI WORK 1 START.
MB ADDR ZONE SCHEDULE MON FRI WORK 2 START
Allows to set a date of commencement of second daily heating period for following days in the schedule:
Monday, Tuesday, Wendesday, Thursday, Friday. Allowable values for the variable fall within a range from
0 to 1425 (00:00 to 23:45). Attempt to record a number beyond the allowable values leads to an error
message. The variable is stored in backed-up EEPROM memory.
MB ADDR ZONE SCHEDULE MON FRI WORK 2 START = h * 60 + m.
16