Indicator Lamps: 

 

„Battery Full“  

Battery (Batteries) fully charged

, green: 

 

If it is lighting:  Battery (batteries) has (have) been charged to 100 %, Float charge, conservation of charge U2, 

 

finished.

 

 

If it is flashing:   Main charging process is effected in the Absorb charge charging phase U1, indication of

 

 

   charging state of approx. 80 % (short flashing), gradual increase to 100 % (long flashing).

 

 

Off:   

Main charging process, Bulk charge, is still being executed in the phase I.

 

 

„Main Charging“  

Main charging, 

yellow: 

 

If it is lighting:  Main charging process is Bulk- or Absorb charge, in the phase I or the charging phase U1.

 

 

Off:   

Float charge, conservation of charge U2.

 

 

If it is flashing:  1.  Disconnection of the battery protection: battery “A” temperature < -40 ° C or temperature 

 

 

rise (depending on type, e.g. 57 ° C or 63 ° C), automatic reset in case of slight cooling off  

 

or 

 

 

2.  External battery overvoltage > 15.50 V (> 31.0 V) after 20 seconds  

      

   

 

automatic reset < 12.75 V (< 25.5 V) after 30 seconds 

 

„Current“ 

 Charging Current, 

red: 

 

The lighting intensity of the LED „Current“ (Charging Current) will be 

reduced or increased depending on the

 

 supplied charging current

 

 „Battery I“,  yellow: 

 

If it is lighting:  Control and charging of main battery „I“.

 

 

Off: 

Output is blocked (safety switch)

 

 

 „Battery II“,  yellow: 

 

If it is lighting:  Control and charging of auxiliary battery „II“.

 

 

Off:   

Output is blocked (safety switch)

 

 

„Power “  

Mains, 

red: 

 

If it is lighting:  Mains supply is available and charger is ready for operation.

 

 

If it is flashing:  1.  Disconnection of safety timer, duration of the charging phase I was too long, too many  

 

 

consumers, battery defective (short-circuit of the cells). Reset is only possible by     

 

 

withdrawing the mains plug.

 

 

2.  Internal unit failure (overheating), automatic reset after cooling down. 

 

 

3.  Wrong polarization of battery (+ and - are mixed up). 

 

Operating Instructions: 

 

 

 

Interruption of the Charging Process: 

In case of a power failure or withdrawal of the mains plug during the charging process, the charging process 
will be interrupted. The connected batteries 

will not be discharged

 by the charger. Thus, the charging process 

can be interrupted at any time.

 

In case of frequent interruptions, particularly before reaching the full charge (LED „Battery Full“ is lighting 

permanently

), the battery should be subject to an 

occasional full charging cycle of 24 hours 

for equalisation 

of the charge. 

 

Lifetime of the battery:  Partially Discharged Batteries:

 

 

In contrast to other battery types, batteries on lead basis 

do not have any

 harmful memory effect. 

Consequently: In case of doubt, partially discharged batteries are to be 

charged fully 

as soon as possible. 

 

Store only fully charged batteries 

and recharge them periodically, particularly in case of used (older) batteries 

and higher temperatures. 

 

Lifetime of the battery:  Recharge totally discharged batteries immediately:

 

 

Sulphation

 of the battery plates due to total discharge is to be prevented by 

immediate charging

, particularly 

in case of low and high ambient temperatures. If the grade of sulphation is not too intensive, the battery can 
recover part of the battery capacity after 

several charging/discharging cycles

 

 

Lifetime of the battery: 

Keep batteries cool; choose an appropriate location for installation. 

 

 

Overvoltage Protection: 

12 V chargers are protected against connection of excessive battery voltage rates or 

will be switched-off in case of defective additional charging systems (solar systems, generators or similar 
systems), switching threshold 15.5 V (31 V), delay 20 s. 

 

Overvoltage Limitation: 

 

Sensitive consumer loads are protected by means of a limitation of the charging voltage to max. 15 V (30 V) 
during all modes of charging. 

 

Overload / Overheating Protection Charger: 

The charger is equipped with a double electronic protection against overload. The unit is equipped with an 
automatic protection against adverse installation conditions (e. g. insufficient ventilation, excessive ambient 
temperatures) by gradual reduction of the charging capacity. 

 

 

Voltage Measurement: 

Measurement of the voltage is to be effected at the battery and not at the charger (loss 

at the charging cables). 

 

 

Содержание Pb 1210 SMT 2B

Страница 1: ...charging current 12 V 24 V 2 A for support charging and conservation of charge of the vehicle s starter battery with overcharge protection Further Characteristics of the Unit The charging voltage is f...

Страница 2: ...condition 6 Installation in a well ventilated room protected from rain humidity dust aggressive battery gas as well as in an environment being free from condensation water Never use the unit at locati...

Страница 3: ...nsor Temperature Sensor Order No 2001 is required The temperature sensor controls battery temperature I and the temperature dependent correction of the charging voltage It is connected to the unit ter...

Страница 4: ...for connection is included in the delivery scope Connection Just insert the plug of the remote control into the tip jack Remote Control of the charger Functioning The remote control is equipped with t...

Страница 5: ...6 mm2 6 mm2 2 x 1 8 3 0 m 6 mm2 10 mm2 10 mm2 10 mm2 10 mm2 reduce wire cross section at the terminal if necessary CAUTION Safety Instructions Mains connection is only allowed to a shock proof socket...

Страница 6: ...2 6 mm2 6 mm2 6 mm2 6 mm2 2 x 1 8 3 0m 6 mm2 10 mm2 10 mm2 10 mm2 10 mm2 reduce wire cross section at the terminal if necessary CAUTION Safety Instructions Mains connection is only allowed to a shock...

Страница 7: ...V 25 C 2 h U3 Full Conservation Storage Charging 13 40 V 26 8 V 25 C Continuous AGM Charging Program for Lead AGM Fleece Batteries Adapted to closed gas tight AGM absorbet glass mat batteries and bat...

Страница 8: ...ing process will be interrupted The connected batteries will not be discharged by the charger Thus the charging process can be interrupted at any time In case of frequent interruptions particularly be...

Страница 9: ...the charging current an unnecessary long U1 phase is avoided which might be caused by consumer load falsifying the charging current The LED Main Charging will stop lighting 4 U2 Phase LED Battery Ful...

Страница 10: ...pensation In case of 24 V operation Multiply all indicated voltage rates by 2 TS Temperature Sensor Charging Program Gel Charging Program AGM Fleece Characteristic Line IU1oU2 Characteristic Line IU1o...

Страница 11: ...rvoltage Disconnection 20 sec 15 5 V 15 5 V 15 5 V 15 5 V 15 5 V Ripple Factor Voltage 50mV rms 50 mV rms 50 mV rms 50 mV rms 50 mV rms Input Battery I Temperature Sensor Yes Yes Yes Yes Yes Charging...

Страница 12: ...corresponds to the following standards or standardized documents EN60335 2 29 EN55014 EN55022 B DIN14685 DIN40839 1 EN61000 3 2 EN61000 3 3 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6...

Отзывы: