background image

--3--

 

Installation of the Unit:

 

 

The charger can be installed 

near Battery I

 (short charging cables) at any location being clean and being protected 

from humidity and dust. Despite the charger's high efficiency, heat is produced, which is brought out of the casing 
by means of the built-in fan.  
Ensure sufficient 

ventilation

 in the 

environment of the unit,

 so that the heat can be carried-off. Protect the unit 

from aggressive battery gas.  
The unit can be installed in any position. However, the 

vent holes

 of the casing should never be covered to ensure 

the full charging capacity (

minimum distance:

 

10 cm

). 

Ensure a solid and vibration reducing installation using 

rubber bushings

 on an even and hard mounting surface. 

 
 
 

Battery Connection and Battery Settings for Start-up: 

 

Observe the connection plan! Observe the cable cross-section and length, as well as the polarization, and insert the 
fuses near the battery. 

First connect the charger

 (it is short circuit-proof), and after that the battery (it is not short circuit-proof). 

 

1.

 

Connect 1 battery to the large terminals „ - “  und  „ + “ observing the correct polarity.

 

2.

 

Set the 

charging program

 for the battery type (technology):  See 

Table

 

1.

 

 

Insert the mains plug (unit rear), and the automatic charging process starts. 

 
 

Option:

  

Several Batteries at Main output Battery I:

 

 

Parallel charging of two or several batteries of the same voltage (12 V) is admissible. The batteries are to be 
„paralleled“, i. e. the „+“ connections of the batteries have to be coupled and should be connected to the „+“ 
connection of the charger. The minus (-) connections have to be coupled in the same way. 

The total capacity (total 

Ah) should not exceed the indicated maximum battery capacity (depending on the case of application). 

According to the battery manufacturers, 

permanent 

parallel operation is admissible in case of two or several 

batteries of the same voltage, type, capacity, as well as of the same age (history) in cross connection.  

 

 
 

Option:  Temperature Sensor

 

(Temperature Sensor, Order No. 2001 is required):

 

 

The temperature sensor controls 

battery temperature I 

and the temperature-dependent correction of the charging 

voltage. It is connected to the unit terminals  

„ T T “

(any polarity). 

 

Installation: 

The 

thermal contact 

of sensor and 

battery I 

(inside temperature) 

should be well

. Thus, it should be screwed to the 

negative pole of the battery. It is also possible to fasten it at the centre of the battery's casing sidewall. Ensure that 
the installation place is not influenced by any source of heat (motor unit, exhaust, heater etc.).

 

 

Effect: 
The temperature-dependent charging voltage of the battery will be adapted automatically to the battery 
temperature (

also refer to

 „Charging Voltage Rates of Battery I and Temperature Compensation“).  

 

The temperature sensor measures the battery temperature. In case of low temperatures (winter operation), the 
charging voltage will be increased in order to improve and accelerate the full charging of the weak battery. Sensitive 
consumers are protected by a limitation of the voltage in case of very low outside temperatures. 
In case of summery temperatures, the charging voltage is reduced to minimize the stress (gassing) of the battery and 
to extend the lifetime of gas-tight batteries.  

 

Battery Protection

 (see Characteristic Lines "charging voltage and temperature compensation"): 

At high temperatures of the battery  (depending on type, for example 54 °C or 58 °C) the charging current will be 
reduced to 50 % as a precaution. If the temperature of the battery rises still further, few ° C higher a complete 
disconnection is issued by the safety switch.  

LED "Main Charging" will be flashing.

 All previous data of 

charging will be recorded. The automatic charging will continued if the temperatures is fallen below the above 
temperatures. The charging process is also blocked at battery temperatures  
below – 40 °C. 

 

 

The charger recognizes automatically a missing sensor, cable break or short-circuit of the sensor lines, 
as well as unreasonable measuring values! In that case, it will switch to the usual nominal voltage rates 
of 20 °C / 25 °C being recommended by the battery manufacturers.

 

 

 
 

 

 

Содержание Pb 1210 SMT 2B

Страница 1: ...charging current 12 V 24 V 2 A for support charging and conservation of charge of the vehicle s starter battery with overcharge protection Further Characteristics of the Unit The charging voltage is f...

Страница 2: ...condition 6 Installation in a well ventilated room protected from rain humidity dust aggressive battery gas as well as in an environment being free from condensation water Never use the unit at locati...

Страница 3: ...nsor Temperature Sensor Order No 2001 is required The temperature sensor controls battery temperature I and the temperature dependent correction of the charging voltage It is connected to the unit ter...

Страница 4: ...for connection is included in the delivery scope Connection Just insert the plug of the remote control into the tip jack Remote Control of the charger Functioning The remote control is equipped with t...

Страница 5: ...6 mm2 6 mm2 2 x 1 8 3 0 m 6 mm2 10 mm2 10 mm2 10 mm2 10 mm2 reduce wire cross section at the terminal if necessary CAUTION Safety Instructions Mains connection is only allowed to a shock proof socket...

Страница 6: ...2 6 mm2 6 mm2 6 mm2 6 mm2 2 x 1 8 3 0m 6 mm2 10 mm2 10 mm2 10 mm2 10 mm2 reduce wire cross section at the terminal if necessary CAUTION Safety Instructions Mains connection is only allowed to a shock...

Страница 7: ...V 25 C 2 h U3 Full Conservation Storage Charging 13 40 V 26 8 V 25 C Continuous AGM Charging Program for Lead AGM Fleece Batteries Adapted to closed gas tight AGM absorbet glass mat batteries and bat...

Страница 8: ...ing process will be interrupted The connected batteries will not be discharged by the charger Thus the charging process can be interrupted at any time In case of frequent interruptions particularly be...

Страница 9: ...the charging current an unnecessary long U1 phase is avoided which might be caused by consumer load falsifying the charging current The LED Main Charging will stop lighting 4 U2 Phase LED Battery Ful...

Страница 10: ...pensation In case of 24 V operation Multiply all indicated voltage rates by 2 TS Temperature Sensor Charging Program Gel Charging Program AGM Fleece Characteristic Line IU1oU2 Characteristic Line IU1o...

Страница 11: ...rvoltage Disconnection 20 sec 15 5 V 15 5 V 15 5 V 15 5 V 15 5 V Ripple Factor Voltage 50mV rms 50 mV rms 50 mV rms 50 mV rms 50 mV rms Input Battery I Temperature Sensor Yes Yes Yes Yes Yes Charging...

Страница 12: ...corresponds to the following standards or standardized documents EN60335 2 29 EN55014 EN55022 B DIN14685 DIN40839 1 EN61000 3 2 EN61000 3 3 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6...

Отзывы: