Troubleshooting
158
Electrical Control System
2.4.4.13. P0 malfunction
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or
close to 0, the IPM is defective. Otherwise, please follow the procedure below:
P6 display
P6 display
IPM module protection
IPM module protection
Yes
Check whether the power voltage
is normal.
Check whether the power voltage
is normal.
Measure whether outdoor terminal
voltage is normal
˛
Measure whether outdoor terminal
voltage is normal
˛
Restart the unit when the power supply
gets normal
Restart the unit when the power supply
gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
˛
Measure whether the voltage
between L and N is normal
˛
Yes
Measure whether input voltage of
bridge rectifier is normal
˛
Measure whether input voltage of
bridge rectifier is normal
˛
No
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of L
and N well or correctly
Check the wiring of L
and N well or correctly
econnect it well
Reconnect it well
Check the wiring of
bridge rectifier well or
correctly
Check the wiring of
bridge rectifier well or
correctly
No
No
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer to the
Appendix
ii
3
˛
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
˛
Replace the bridge rectifier
Replace the bridge rectifier
No
Check whether bridge
rectifier is normal
C
Check whether bridge
rectifier is normal
Check the wiring of reactor
or inductance
C
r
Check the wiring of reactor
or inductance
Reconnect the wiring
Reconnect the wiring
No
Check whether reactor or
inductance is normal
Check whether reactor or
inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Reconnect it well
Reconnect it well
No
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the refrigerant system is ok
Check whether the refrigerant system is ok
No
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is
normal
Check the compress is
normal
Yes
Replace the compressor
Replace the compressor
No
Replace IPM board
Replace IPM board
Replace the outdoor main PCB
Replace the outdoor main PCB
No
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Reconnect it well
Reconnect it well
No
Yes
Yes
P0
Содержание ACP-12CC35AERI
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Страница 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 33: ...Wiring Diagrams Indoor Units 29 ...
Страница 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Страница 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Страница 44: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Страница 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Страница 58: ...Features 54 Indoor Units ...
Страница 60: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Страница 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Страница 69: ...Console Type Console Type 65 2 Dimensions 1 6 D r a i n p i p e 195 Hanging arm Unit mm 700 600 210 ...
Страница 70: ...Console Type 66 Console Type 3 Service Space ...
Страница 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Страница 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Страница 77: ...Console Type Console Type 73 ...
Страница 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Страница 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Страница 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Страница 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Страница 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Страница 113: ...Refrigerant pipe installation Installation 109 ...
Страница 176: ......
Страница 177: ...ZZZ 9 9 FRP ...