Electrical Control Function
120
Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Temperature protection of compressor discharge
For 12K units:
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
---Compressor discharge temp. T5>115
đ
for 5s, compressor stops and restarts up till T5<90
đ
---110<T5<115
đ
, decrease the frequency to the lower level every 2 minutes.
---105<T5<110
đ
, keep running at the current frequency.
----T5<105
đ
, no limit for frequency.
For other units:
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102
đ
<T5<115
đ
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
đ
for 10 seconds, the compressor will stop and restart till T5<90
đ
.
1.2.4 Sensor protection at open circuit and breaking disconnection.
1.2.5 Indoor fan delayed open function
For M floor-standing:
When the unit starts up, the louver will be active immediately and the indoor fan will open 5s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
For other models:
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.6 Fan speed is out of control(for units used DC motor)
For super slim cassette: When indoor fan speed keeps too low (lower than 200RPM) for 50s, the unit will
stop and the LED will display the failure.
For M floor-standing: When indoor fan speed keeps too low (lower than 300RPM) for 10s, the unit will stop
and the LED will display the failure.
For other models: When indoor fan speed keeps too low (lower than 300RPM) for 50s, the indoor fan will
shut off and restart 30s later, if protection happened 3 times when fan motor restart continuously, the unit will
stop and the LED will display the failure.
Содержание ACP-12CC35AERI
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Страница 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 33: ...Wiring Diagrams Indoor Units 29 ...
Страница 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Страница 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Страница 44: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Страница 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Страница 58: ...Features 54 Indoor Units ...
Страница 60: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Страница 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Страница 69: ...Console Type Console Type 65 2 Dimensions 1 6 D r a i n p i p e 195 Hanging arm Unit mm 700 600 210 ...
Страница 70: ...Console Type 66 Console Type 3 Service Space ...
Страница 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Страница 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Страница 77: ...Console Type Console Type 73 ...
Страница 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Страница 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Страница 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Страница 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Страница 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Страница 113: ...Refrigerant pipe installation Installation 109 ...
Страница 176: ......
Страница 177: ...ZZZ 9 9 FRP ...