Drainage pipe installation
Installation
111
6.2.3 Individual design of drainage pipe system
¾
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater
pipe and drainage pipe in building.
¾
The drainage pipe of the indoor unit with water pump should be apart from the one without water
pump.
6.2.4 Supporter gap of drainage pipe
¾
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
¾
Each vertical pipe shall be equipped with not less than two hangers.
¾
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
¾
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
¾
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
¾
If the indoor unit has high extra static pressure and without water pump to elevate the condensate
water, such as high extra static pressure duct unit , the water storage pipe should be set to avoid
converse flow or blow water phenomena.
Содержание ACP-12CC35AERI
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Страница 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 33: ...Wiring Diagrams Indoor Units 29 ...
Страница 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Страница 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Страница 44: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Страница 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Страница 58: ...Features 54 Indoor Units ...
Страница 60: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Страница 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Страница 69: ...Console Type Console Type 65 2 Dimensions 1 6 D r a i n p i p e 195 Hanging arm Unit mm 700 600 210 ...
Страница 70: ...Console Type 66 Console Type 3 Service Space ...
Страница 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Страница 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Страница 77: ...Console Type Console Type 73 ...
Страница 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Страница 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Страница 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Страница 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Страница 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Страница 113: ...Refrigerant pipe installation Installation 109 ...
Страница 176: ......
Страница 177: ...ZZZ 9 9 FRP ...