Troubleshooting
Electrical Control System
153
2.4.4.8. J5 malfunction
hether the wiring
between the high pressure
switch and main control
board is connected well or
correctly
Whether the wiring
between the high pressure
switch and main control
board is connected well or
correctly
Method:
Disconnect the plug.
Measure the resistance of
the
high pressure protector, if
the protector is normal the
value is o,
Method:
Disconnect the plug.
Measure the resistance of
the
high pressure protector, if
the protector is normal the
value is o,
Yes
Yes
Connect it well
Connect it well
No
eplace high pressure protector
Replace high pressure protector
No
Whether the high
pressure protector
is broken
Whether the high
pressure protector
is broken
heck whether the outdoor
ambient temperature is
higher than 50
ć
Check whether the outdoor
ambient temperature is
higher than 50
ć
No
top the unit
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Check whether the refrigerant
system is ok
Replace outdoor main
board
Replace outdoor main
board
No
P1 display
P1 display
High pressure protection
High pressure protection
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
lease refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
NO
J5
Содержание ACP-12CC35AERI
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Страница 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 33: ...Wiring Diagrams Indoor Units 29 ...
Страница 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Страница 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Страница 44: ...Service Space 40 Indoor Units 3 Service Space ...
Страница 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Страница 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Страница 58: ...Features 54 Indoor Units ...
Страница 60: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Страница 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Страница 69: ...Console Type Console Type 65 2 Dimensions 1 6 D r a i n p i p e 195 Hanging arm Unit mm 700 600 210 ...
Страница 70: ...Console Type 66 Console Type 3 Service Space ...
Страница 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Страница 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Страница 77: ...Console Type Console Type 73 ...
Страница 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Страница 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Страница 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Страница 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Страница 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Страница 113: ...Refrigerant pipe installation Installation 109 ...
Страница 176: ......
Страница 177: ...ZZZ 9 9 FRP ...