Module status
gives you detailed information about the error that
occurred at a module.
The
Module status
may be activated via the parameterization and has the
following structure:
Module status
Byte
Bit 7 ... Bit 0
X
Bit 5 ... 0: 001100 (fix) Length of the Module status
Bit 7 ... 6: 00 (fix) Code for Module status
X+1
82h (fix) Status type: Module status
X+2 00h
(fix)
X+3 00h
(fix)
X+4
For slot 1 ... 20 the following error are specified:
00: Module has valid data
01: Module error - invalid data (Module defective)
10: Incorrect module - invalid data
11: No Module - invalid data
Bit 1, 0: Module status module at slot 1
Bit 3, 2: Module status module at slot 2
Bit 5, 4: Module status module at slot 3
Bit 7, 6: Module status module at slot 4
X+5
Bit 1, 0: Module status module at slot 5
Bit 3, 2: Module status module at slot 6
Bit 5, 4: Module status module at slot 7
Bit 7, 6: Module status module at slot 8
X+6
Bit 1, 0: Module status module at slot 9
Bit 3, 2: Module status module at slot 10
Bit 5, 4: Module status module at slot 11
Bit 7, 6: Module status module at slot 12
X+7
Bit 1, 0: Module status module at slot 13
Bit 3, 2: Module status module at slot 14
Bit 5, 4: Module status module at slot 15
Bit 7, 6: Module status module at slot 16
X+8
Bit 1, 0: Module status module at slot 17
Bit 3, 2: Module status module at slot 18
Bit 5, 4: Module status module at slot 19
Bit 7, 6: Module status module at slot 20
Module status