4-7
Project engineering DP slave
For project engineering a DP master engineering tool may be used like the
Siemens SIMATIC manager. Here you assign the according Profibus DP
slave modules to the DP master. A direct assignment takes place via the
Profibus address that you set at the DP slave address selector.
By installing the according GSD file the IM 306 DP slave is listed at the
hardware catalog as "VIPA_306-1LE00 [DPV...]":
Profibus DP
> Additional Field devices > I/O VIPA_306_1XX00
VIPA serves GSD files for the IM 306 DP slave. Depending on the installed
GSD file the following modules are embedded to the hardware catalog:
Slave type
GSD file
DP-V0 VI100BB4.GSD
DP-V1 VI110BB4.GSD
Install the appropriate GSD file in your engineering tool. For more
information see the manual of you engineering tool.
•
Mount your Profibus system.
•
Start your project engineering tool with a new project.
•
Configure a master system and create a new Profibus subnet.
•
For the project engineering of the IM 306 DP slave take the
"VIPA 306-1LE00 (DPVx)" for each functionality from the hardware
catalog and drag it to the DP master subnet.
•
Enter a Profibus address between 2 and 125 into the properties of the
DP slave and set the same address at the address lever.
•
Parameterize the DP slave. More may be found at
"DP-Vx slave parameterization".
•
Configure your Siemens S5 rack. More may be found at
"DP slave configuration".
•
Transfer your project to the CPU.
General
DP-V0/DP-V1
functionality by
GSD file
IM 306-1LE00
Project
engineering
Содержание IM 306-1LE00
Страница 2: ......
Страница 6: ...Contents Manual VIPA Accessories ii HB37E IM RE_306 1LE00 Rev 09 28...
Страница 34: ...Chapter 3 Hardware description Manual VIPA Accessories 3 6 HB37E IM RE_306 1LE00 Rev 09 28...
Страница 58: ...Index Manual VIPA Accessories A 2 HB37E IM RE_306 1LE00 Rev 09 28 M Stich...