3. Technical specification 

Table 1 - Electrical specifications 

Mains supply 

230V AC  +10% - 15%  (100 Watts maximum) 

 

Mains supply fuse 

1.6Amp (F1.6A L250V) 

Replace only with similar type 

Power supply rating 

3 Amps total including battery charge 28V +/ 2V 

 

Maximum ripple current 

1.5 Volts 

 

Output voltage 

18.5 to 29V DC +/- 2% 

 

Imax a 

400 milliamps 

 

Imax b 

2.3 Amps 

 

Imin 

0.065A 

 

Battery type (Yuasa NP) 

Two 12 Volt sealed lead acid (7Ah maximum) 

See table 2 for capacities 

Battery charge voltage 

27.6VDC nominal (temperature compensated) 

See table 3  

Battery charge current 

0.7A maximum 

 

Battery lead fuse 

20mm, 3.15A glass 

Replace only with the same type 

Battery high impedance warning 
(Rimax) 

1.35 ohms max 

 

Low battery voltage indication 

21V +/- 2% 

 

Low battery shut off voltage 

18.5V +/- 2% 

 

Maximum current draw from batteries 

3 Amps 

With main power source disconnected 

R0V output 

Fused at  with electronic fuse 

 

Dedicated sounder outputs 

24V Fused at 500mA with electronic fuse 

1.6 Amp total load over all circuits 

Fault relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Alarm relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Local alarm relay contact rating 

30VDC 1A Amp maximum for each 

Maximum ratings not to be exceeded 

Zone quiescent current 

1.6mA maximum 

See table 4 for detector types 

Terminal capacity 

0.5mm

2

 to 2.5mm

2  

solid or stranded wire 

 

Number of detectors per zone 

> 20  

Dependent on type 

Number of sounders per circuit 

Dependent on type and current consumption 

See table 6 for sounder types 

Detection circuit end of line 

6K8 5% ½ Watt resistor 

Supplied in terminals 

Sounder circuit end of line 

10K 5% ¼ Watt resistor 

Supplied in terminals 

No. of detection circuits 

 (see table 2 for number of zones for each model) 

Dependent on model 

No. of sounder outputs 

2 (plus one per zone on T models) 

 

SIL, AL, FLT, RST inputs 

Switched -ve, max resistance 100 Ohms 

 

Zone normal threshold 

8K ohm TO 1K ohm 

 

Detector alarm threshold 

999 ohms to 400 ohms 

 

Short circuit threshold 

99 ohms to 0 ohms 

 

 

Table 2 - Standby battery capacity required for fully loaded system 

Panel model 

24 hours 
standby 

48 hours standby 

72 hours 
standby 

Standby current 

Max panel alarm 
current 

HSCP-S-2 (2 Zones) 

3Ah 

4.6Ah 

6.2Ah 

0.065 

0.10A 

HSCP-S-4 (4 Zones) 

3.3Ah 

5.1Ah 

6.9Ah 

0.075 

0.21A 

HSCP-S-8 (8 Zones) 

3.75Ah 

5.95Ah 

8.2Ah 

0.093A 

0.55A 

 
Table 3 - Battery charge voltage versus temperature

 

Temperature 

0

Battery charge voltage 

29.2

 

10 

28.56

 

20 

27.99

 

30 

27.55

 

40 

27.13

 

 

 

Table 4 - Compatible sounders 

Model 

Type 

Manufacturer 

Comments 

BANSHEE 

ELECTRONIC 

VIMPEX 

 

WAFER 

ELECTRONIC 

VIMPEX 

 

FIRECRYER RANGE 

ELECTRONIC VOICE 

VIMPEX 

 

KOBISHI 

MOTORISED 

VIMPEX 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: