background image

Man-1131_Hydrosense_HSCP_01 

     Page 14 of 18

 

A1* 

ZONE 1 ANY ALARM DELAYED 

A2* 

ZONE 2 ANY ALARM DELAYED 

A3* 

ZONE 3 ANY ALARM DELAYED 

A4* 

ZONE 4 ANY ALARM DELAYED 

A5* 

ZONE 5 ANY ALARM DELAYED 

A6* 

ZONE 6 ANY ALARM DELAYED 

A7* 

ZONE 7 ANY ALARM  DELAYED 

A8* 

ZONE 8 ANY ALARM DELAYED 

Zone needs to be triggered for 30 seconds continuously 
before an alarm is generated.  
 

 

 

 

C1 

ZONE 1 SOUNDERS INHIBITED 

C2 

ZONE 2 SOUNDERS INHIBITED

 

C3 

ZONE 3 SOUNDERS INHIBITED

 

C4 

ZONE 4 SOUNDERS INHIBITED

 

C5 

ZONE 5 SOUNDERS INHIBITED

 

C6 

ZONE 6 SOUNDERS INHIBITED

 

C7 

ZONE 7 SOUNDERS INHIBITED

 

C8 

ZONE 8 SOUNDERS INHIBITED

 

Enables  individual  zones  to  be  configured  not  to  operate  zonal 
sounders. 
On 2 wire “T” series panels this enables individual zones to be 
configured  for  use  with  conventional  (non  2-wire)  detector 
bases. 
 
 
SOFTWARE VERSIONS SIGMA242.HEX and above only 

 

 

 

E1* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY 

E2* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E3* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E4* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E5* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E6* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E7* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

E8* 

ZONE 1 WILL NOT OPERTATE ALARM RELAY

 

Enables individual zones to be selected to not operate the alarm 
relay.  This  is  sometimes  combined  with  the  non-latching 
function to prevent ring around on interconnected panels. 
 
 
 
 
 

 

Once  the  required  configuration  options  have  been  set,  the  Write  enable  switch 

must

  be  returned  to  its 

normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned 

off. 

16. Watchdog reset switch 

If  for  any  reason  the  microprocessor  in  the  control  panel  fails  to  carry  out  its  operation  correctly  it  will 

attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate 

these events. 
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front 

panel, the CPU fault LED inside the panel.  

This  fault  can  only  be  cleared  by  pressing  the  WATCHDOG  RESET  button  on  the  PCB  inside  the  control 
panel. The control panel buzzer can not be silenced and will continue to sound until the watchdog activation 

is reset. 

 

17. Processor reset switch 

Once  started,  the  microprocessor  controlling  the  panel  should  continue  to  run  continuously  without 

interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET 
button on the PCB inside the control panel. 

This should not normally be necessary but should be done as a matter of course if the system is behaving 

abnormally.  The  system  should  resume  normal  operation  within  a  couple  of  seconds  of  pressing  the 

processor reset button. 

 
18. Internal indications – troubleshooting 

To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of 
internal indicators are visible with the front cover removed as follows: 

 

18.1 Mains fail 

Indicates that the 230V AC supply is not present and the system is running on standby batteries. 

If there is not a power cut, check the panels mains fuse. 

 

18.2 Batt fail 

Indicates that the standby battery has become disconnected or that the charging circuit of the control panel 

has a high resistance or has failed. Check that both batteries are connected and linked together. Test 

battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads. 
 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: