background image

Man-1131_Hydrosense_HSCP_01 

     Page 15 of 18

 

18.3 CPU fault 

Indicates that the central processor unit has failed to correctly execute code and has been re-started by the 
system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition. 

Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs 

the circuit board replacing. (See maintenance section). 

 

18.4 Aux 24V fault 

The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power alarm ancillary 

equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output 
has been exceeded. The fuse is a self resetting type and the supply will resume when the fault condition is 

removed. 

 
18.5 Batt low 

Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the 

minimum battery voltage). 

 

18.6 Earth fault 

Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect 

cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on. 
 

18.7 Sys fuse fault 

Indicates that the total power rating of the power supply has been exceeded and that the system fuse has 

come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips 
fuse to identify troublesome circuit. 

 

18.8 S1 fault and S2 fault 

Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors.  Check 

sounder circuit wiring. 

 

18.9 Comms fault 

Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault 

at all repeaters and ancillary boards to identify the source of the problem. 

 

19. Power supply 

The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the 

fused terminal block labelled “230V”. 
The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar 

type. 

The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum 

0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse 
rated at 4 Amps. 

The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at 

least 50mm. 
Mains wiring should include an earth conductor which is securely bonded to the building earth and should 

enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short 

inside the enclosure and secured together close to the mains terminal block with a cable tie. 
The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see 

table 2 for battery size required for each model). 

The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps. 

Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB 
is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit which must only be replaced 

with one of the same type. 

It is most important that the polarity of the batteries is carefully observed when connecting.  
When  the  batteries  are  discharged  to  a  level  at  which  a  low  battery  indication  is  given,  the  BATT  FAIL 

indicator will also be lit. 

 

Wrongly connected batteries could cause damage to the control panel. 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: