Man-1131_Hydrosense_HSCP_01
Page 12 of 18
14.10.3 Activate delays
To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears
on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will
have their alarm outputs delayed by the time set in configuration options 00 to 09.
14.10.4 Disable fault contact
The fault relay can be disabled by selecting configuration option 22.
14.11 Test mode
The HYDROSENSE HSCP range of panels enable the system to be tested single handed by using a test mode.
When in test mode, activation of a water detector will be automatically reset (after drying the detector)
within a few seconds to eliminate the need to return to the control panel to reset after every activation.
Test mode is entered in a similar way to disablements. With the
Enable Control
key inserted, press the
Mode
button until “t” appears in the first of the seven segment displays. Then press the
Select
button until the
required zone number appears. Pressing the
Enter
button will cause the
Test
and
Zone Fault
LEDs to
illuminate indicating the zones which are in test mode.
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db"
function (for example) toggles between sounders disabled and sounders enabled.
15. Configuration options
The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time
of commissioning to suit the requirements of the installation. These options are normally set once and will
rarely need to change. The configuration options are only available at access level 3.
To access level 3, CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate)
to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will
“pip” three times every few seconds as an indication that it is at this access level.
Configuration options are simple to enter using the codes in table 8 below. When the control panel is at
access level 3, the sub-text of the
Mode
and
Select
buttons is used to enter a number using tens (+10) and
units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units,
seven segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1
to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
Figure 8 – Access level 3 (Write enable) enable switch location
Figure 9 – Example display showing option set and not set.
DOT
FLASHING
NO DOT
ZONE 1 NON
LATCHING
ZONE 1 NON
NORMAL