Man-1131_Hydrosense_HSCP_01 

     Page 12 of 18

 

14.10.3 Activate delays 

To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears 
on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will 

have their alarm outputs delayed by the time set in configuration options 00 to 09. 

 

14.10.4 Disable fault contact 

The fault relay can be disabled by selecting configuration option 22.  

 

14.11 Test mode 

The HYDROSENSE HSCP range of panels enable the system to be tested single handed by using a test mode. 

When  in  test  mode,  activation  of  a  water  detector  will  be  automatically  reset  (after  drying  the  detector) 

within a few seconds to eliminate the need to return to the control panel to reset after every activation. 
Test mode is entered in a similar way to disablements. With the 

Enable Control

 key inserted, press the 

Mode

 

button until “t” appears in the first of the seven segment displays. Then press the 

Select 

button until the 

required  zone  number  appears.  Pressing  the 

Enter 

button  will  cause  the

  Test 

and

  Zone  Fault 

LEDs  to 

illuminate indicating the zones which are in test mode. 
Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" 

function (for example) toggles between sounders disabled and sounders enabled. 

15. Configuration options 

The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time 

of commissioning to suit the requirements of the installation. These options are normally set once and will 

rarely need to change. The configuration options are only available at access level 3.  

To access level 3, CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) 
to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will 

“pip” three times every few seconds as an indication that it is at this access level. 

 
 

 

 

 

 

 

 

 

 

 
 

 

 
Configuration options  are simple  to  enter  using  the  codes in  table  8  below.  When  the  control  panel is  at 

access level 3, the sub-text of the 

Mode

 and 

Select

 buttons is used to enter a number using tens (+10) and 

units (+1).  
When  the  required  code  number  is  displayed,  pressing  the  enter  button  will  cause  the  dot  on  the  units, 
seven segment display to flash. This indicates that a configuration option has been set.  
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 

to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set. 
 

 

 

 

 

 

 

 

 

 
 

 

 

Figure 8 – Access level 3 (Write enable) enable switch location 

Figure 9 – Example display showing option set and not set. 

 

DOT 

FLASHING

NO DOT

ZONE 1 NON 

LATCHING

ZONE 1 NON 

NORMAL

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: