background image

Man-1131_Hydrosense_HSCP_01 

     Page 17 of 18

 

This enables each zone to be given a text description allowing easier identification of any zones showing an 

abnormal condition. 

 

 

 
 

 

 

 
 

 

 
 

 

 
 

 

 
 

 

 
 

 

 
 

 

22. Hydrowire commissioning details  
 

22.1 Installation   

22.1.1 Lengths of Hydrowire should be laid on the floor in the protected area such that the distance 

between any two Hydrowires is no more than 2 metres. 
 

22.1.2 For localised protection of sources of potential water leakage, such as air conditioning 

systems or water filled radiators, the distance between Hydrowires may be greater. 
 

22.1.3 The cable should be installed such that it remains in contact with the floor along as much of 

its length as possible. This may require the use of P clips, particularly in areas where the 
cable may be disturbed. 

 

22.1.4 Although the construction is quite sturdy, the cable may be damaged by crushing or excessive 

bending. A bend radius of 150 mm is recommended as a minimum. 
 

22.1.5 The end of the Hydrowire must be terminated with an end of line plug (K2110). 

 
22.1.6 The terminating connection box (K2106) should be secured to the wall or floor such that the 

Hydrowire does not have to be stretched or pulled to reach it. 

 

22.1.7 The installed Hydrowire should consist of a K2106 connection box, Hydrowire cable (K2104 or/and 
K2105) and end of line plug unit (K2110). 

 

22.1.8 The red warning label should be left such that it is clearly visible. 
 

22.1.9 Hydrowire should not come into contact with surface temperatures greater than 70°C. 

 

22.1.10 Lengths greater than 50 metres are not allowed. 
 

22.2 Connection to Control Panel   

22.2.1 The K1622 connection box, when triggered presents an impedance of 470 R to the 24 volt 
circuit from the control panel. 

 ZONE DESIGNATION LABEL 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: