background image

Man-1131_Hydrosense_HSCP_01 

     Page 13 of 18

 

Table 8 – Configuration codes

 

 

CODE  

FUNCTION 

COMMENTS 

00 

SOUNDER DELAY TIME = 30 SECONDS 

01 

SOUNDER DELAY TIME = 1 MINUTE 

02 

SOUNDER DELAY TIME = 2 MINUTES 

03 

SOUNDER DELAY TIME = 3 MINUTES 

04 

SOUNDER DELAY TIME = 4 MINUTES 

05 

SOUNDER DELAY TIME = 5 MINUTES 

06 

SOUNDER DELAY TIME = 6 MINUTES 

07 

SOUNDER DELAY TIME = 7 MINUTES 

08 

SOUNDER DELAY TIME = 8 MINUTES 

09 

SOUNDER DELAY TIME = 9 MINUTES 

Sets the time delay before sounders operate in combination with 
configuration codes 31 to 48 and access level 2 function AD. 
 

10 

COMMON ALARM MODE (default) 

All sounders operate upon any alarm condition 

11 

TWO-STAGE ALARM MODE 

Continuous sounders in activated zone, pulsing elsewhere 

12 

ZONED ALARM MODE 

Only sounders connected to zone in alarm operate 

 

 

 

21* 

DISABLE ALARM BUZZER 

Buzzer will not operate on alarm condition 

22* 

DISABLE FAULT OUTPUT 

Fault relay will not operate except upon total power failure 

23 

DISABLE EARTH FAULT MONITORING 

Connection of alarm wiring will not announce a fault  

24 

PULSED REMOTE CONTROL OUTPUT 

Aux 24V supply pulses 1 sec on/1 sec off 

25 

ENABLE SOUNDERS ON DETECTION CIRCUITS 

Set if using sounder extension boards 

26 

DISABLE ALARM OUTPUT 

Alarm relay will not operate upon any alarm 

27 

REMOVE AUX 24 UPON PANEL RESET 

24V supply switches off for about 5 seconds when panel is reset 

28 

NOT USED 

 

29 

DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE 

Silenced  sounders  will  not  re-sound  upon  further  zone 
activations 

 

 

 

31 

ZONE 1 ALARM FROM DETECTOR DELAYED 

32 

ZONE 2 ALARM FROM DETECTOR DELAYED

 

33 

ZONE 3 ALARM FROM DETECTOR DELAYED

 

34 

ZONE 4 ALARM FROM DETECTOR DELAYED

 

35 

ZONE 5 ALARM FROM DETECTOR DELAYED

 

36 

ZONE 6 ALARM FROM DETECTOR DELAYED

 

37 

ZONE 7 ALARM FROM DETECTOR DELAYED

 

38 

ZONE 8 ALARM FROM DETECTOR DELAYED

 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by detector only. 
Note:  Access  level  2  function  Ad  must  be  set  for  this  to  take 
effect. 

 

 

 

 

 

 

 

 

 

51 

COINCIDENCE ZONE 1 

52 

COINCIDENCE ZONE 2 

53 

COINCIDENCE ZONE 3 

54 

COINCIDENCE ZONE 4 

55 

COINCIDENCE ZONE 5 

56 

COINCIDENCE ZONE 6 

57 

COINCIDENCE ZONE 7 

58 

COINCIDENCE ZONE 8 

Zone  contributes  to  ancillary  board  coincidence  O/P.  Any 
number of zones can be selected to contribute. 

 

 

 

CODE  

FUNCTION 

COMMENTS 

71* 

ZONE 1 SHORT CIRCUIT INDICATES ALARM 

72* 

ZONE 2 SHORT CIRCUIT INDICATES ALARM

 

73* 

ZONE 3 SHORT CIRCUIT INDICATES ALARM

 

74* 

ZONE 4 SHORT CIRCUIT INDICATES ALARM

 

75* 

ZONE 5 SHORT CIRCUIT INDICATES ALARM

 

76* 

ZONE 6 SHORT CIRCUIT INDICATES ALARM

 

77* 

ZONE 7 SHORT CIRCUIT INDICATES ALARM

 

78* 

ZONE 8 SHORT CIRCUIT INDICATES ALARM

 

Changes the trigger threshold of the 
zone so that the control panel can be 
used on older systems that had no short 
circuit monitoring. 

 

 

 

81* 

ZONE 1 NON-LATCHING 

82* 

ZONE 2 NON-LATCHING 

83* 

ZONE 3 NON-LATCHING 

84* 

ZONE 4 NON-LATCHING 

85* 

ZONE 5 NON-LATCHING 

86* 

ZONE 6 NON-LATCHING 

87* 

ZONE 7 NON-LATCHING 

88* 

ZONE 8 NON-LATCHING 

Renders the zone self-resetting so that 
it can be used to receive signals from  
other systems and will reset when the 
input is removed. 
Note: It can take up to 20 seconds for zone to reset itself when 
sounders are operating 

 

 

 

91 

ZONE 1 DOES NOT SOUND ALARMS 

92 

ZONE 2 DOES NOT SOUND ALARMS

 

93 

ZONE 3 DOES NOT SOUND ALARMS

 

94 

ZONE 4 DOES NOT SOUND ALARMS

 

95 

ZONE 5 DOES NOT SOUND ALARMS

 

96 

ZONE 6 DOES NOT SOUND ALARMS

 

97 

ZONE 7 DOES NOT SOUND ALARMS

 

98 

ZONE 8 DOES NOT SOUND ALARMS

 

Prevents  the  zone  from  operating  the  two  common  sounder 
outputs. 
 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Hydrosense HSCP

Страница 1: ...Hydrosense HSCP Conventional Water Detection Control Panel Operation and Maintenance Manual Man 1131 Issue 01 November 2009 www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...Panel operation 11 15 Configuration options 12 16 Watchdog reset switch 14 17 Processor reset switch 14 18 Internal indications troubleshooting 14 18 1 Mains fail 14 18 2 Batt fail 14 18 3 CPU fault...

Страница 3: ...lass 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requireme...

Страница 4: ...Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See table 4 for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Depende...

Страница 5: ...hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box towards you With the fascia removed there...

Страница 6: ...e enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with H...

Страница 7: ...Any unused zones must have the 6K8 resistor in place When using Probes the 6K8 Resistor must be placed across the terminal wiring as illustrated in the diagram below Detection zone circuits must be w...

Страница 8: ...ailable for powering sounders with a maximum load of 0 41 Amps on any one circuit 9 Connection to remote control terminals Some functions of the control panel can be controlled externally from the pan...

Страница 9: ...n any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activatio...

Страница 10: ...boards share the same address Apply power to main panel and all ancillary boards then briefly press the PROCESSOR RESET button on the main panel wait for a few seconds and the main panel will show th...

Страница 11: ...and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits 14 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the char...

Страница 12: ...een sounders disabled and sounders enabled 15 Configuration options The HYDROSENSE HSCP range of control panels has many configuration options which can be set at the time of commissioning to suit the...

Страница 13: ...AYED 36 ZONE 6 ALARM FROM DETECTOR DELAYED 37 ZONE 7 ALARM FROM DETECTOR DELAYED 38 ZONE 8 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s t...

Страница 14: ...n the control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watc...

Страница 15: ...ary board Check for comms fault at all repeaters and ancillary boards to identify the source of the problem 19 Power supply The control panel requires a 230V 10 15 50 60Hz AC mains power supply which...

Страница 16: ...Detection System will identify any malfunction of the control panel and any malfunction should be reported to the alarm maintenance company immediately Should the control panel become faulty the comp...

Страница 17: ...ugh the construction is quite sturdy the cable may be damaged by crushing or excessive bending A bend radius of 150 mm is recommended as a minimum 22 1 5 The end of the Hydrowire must be terminated wi...

Страница 18: ...thumb and forefinger into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an immediate indication at the control pan...

Отзывы: