Man-1131_Hydrosense_HSCP_01
Page 13 of 18
Table 8 – Configuration codes
CODE
FUNCTION
COMMENTS
00
SOUNDER DELAY TIME = 30 SECONDS
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
Sets the time delay before sounders operate in combination with
configuration codes 31 to 48 and access level 2 function AD.
10
COMMON ALARM MODE (default)
All sounders operate upon any alarm condition
11
TWO-STAGE ALARM MODE
Continuous sounders in activated zone, pulsing elsewhere
12
ZONED ALARM MODE
Only sounders connected to zone in alarm operate
21*
DISABLE ALARM BUZZER
Buzzer will not operate on alarm condition
22*
DISABLE FAULT OUTPUT
Fault relay will not operate except upon total power failure
23
DISABLE EARTH FAULT MONITORING
Connection of alarm wiring will not announce a fault
24
PULSED REMOTE CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
Set if using sounder extension boards
26
DISABLE ALARM OUTPUT
Alarm relay will not operate upon any alarm
27
REMOVE AUX 24 UPON PANEL RESET
24V supply switches off for about 5 seconds when panel is reset
28
NOT USED
29
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
Silenced sounders will not re-sound upon further zone
activations
31
ZONE 1 ALARM FROM DETECTOR DELAYED
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Access level 2 function Ad must be set for this to take
effect.
51
COINCIDENCE ZONE 1
52
COINCIDENCE ZONE 2
53
COINCIDENCE ZONE 3
54
COINCIDENCE ZONE 4
55
COINCIDENCE ZONE 5
56
COINCIDENCE ZONE 6
57
COINCIDENCE ZONE 7
58
COINCIDENCE ZONE 8
Zone contributes to ancillary board coincidence O/P. Any
number of zones can be selected to contribute.
CODE
FUNCTION
COMMENTS
71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
74*
ZONE 4 SHORT CIRCUIT INDICATES ALARM
75*
ZONE 5 SHORT CIRCUIT INDICATES ALARM
76*
ZONE 6 SHORT CIRCUIT INDICATES ALARM
77*
ZONE 7 SHORT CIRCUIT INDICATES ALARM
78*
ZONE 8 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the
zone so that the control panel can be
used on older systems that had no short
circuit monitoring.
81*
ZONE 1 NON-LATCHING
82*
ZONE 2 NON-LATCHING
83*
ZONE 3 NON-LATCHING
84*
ZONE 4 NON-LATCHING
85*
ZONE 5 NON-LATCHING
86*
ZONE 6 NON-LATCHING
87*
ZONE 7 NON-LATCHING
88*
ZONE 8 NON-LATCHING
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset itself when
sounders are operating
91
ZONE 1 DOES NOT SOUND ALARMS
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs.