1 1 . 2 F r e q u e n c y o f m a i n t e n a n c e
Comply at a minimum with the legal obligations.
The following table gives an indication of the average maintenance frequencies.
It does not take into account specific factors such as inside or outside installation, the intensity of the at
-
mospheric pollution, the number of occupants, or the number of hours of operation.
B o d y
A t c o m m i s s i o n i n g
M i n i m u m o f e v e r y 6 m o n t h s
Filter
Check for clogging - Clean
Remove dust or replace
Fan
Check the connections - the direction of
rotation
Check the clogging - cleaning if needed
Electrical cabinet
Check the connections
Check the connections
Electrical heater
Check the connections
Check the connections
Water coil
Inspect the sealing
Check the clogging - clean if necessary.
Inspect the sealing / tighten connections
Droplet separator
Clean
Condensate drain tray
Inspect the sealing/flow
Clean
Pressure switches
Check the electrical/aeraulic connections
Check setting for 1 or 2 filters
Check the operation
Sensors
Check the operation/settings
Check the operation/settings
Flexible sleeves
Check they are correctly mounted and
sealed.
Replace if necessary
Fresh air intake/extract grill
Check their existence and their
attachments.
Clean
Duct networks
Check they are correctly connected and
sealed.
Clean
Nozzles/diffusers/plenums
Check the sealing of connections
Clean
1 1 . 3 Li s t o f f a u l t s
In the event of the appearance of a fault or alarm, a message "Maintenance required" appears in red on
the main screen. The type of alarm can then be consulted in the advanced menu, the fault is then clearly
identified on the screen. The list of fault messages is given below.
Note: The alarms are reported with a type C alarm class, and the reset is automatic as soon as the problem
is resolved (no manual acknowledgment is required).
Select advance menu
Screen menu :
Settings menu access
Advanced parameters
Single air flow unit
2012-11-12
System : Normal Fonct.
C:24.0C/R: 17.8C
Select alarm symbol to
display the text of the alarm
detected.
Advanced parameters
6. Pressostat
filter
27 August 14:33 Class:C
Alarm list can be checked
using up and down arrows.
To exit screen, press top
right icon.
Menu
21.4°C
2012-06-26 14:02
2500 m3 /h
Run mode : ON
Temperature setpoint