Su s p e n d e d m o u n t i n g
F l o o r m o u n t
H mini > H
H
L mini > L
L
H mini > H
L mini > L
H
L
3 . 4 . 1 Su p e n d e d c e i l i n g i n s t a l l a t i o n K SC R 0 8 - 1 8 - 2 8 - 3 8
If KSDR 08, 18, 28 or 38 is attached to the ceiling, install beforehand the four delivered security legs of
the cover. They allow it to be moved to the side to open the filter passage. It is sufficient then to extract it
for replacement by a new filter.
To completely remove the cover, slide it sideways.
Cover fixing legs setting
Unscrew the eight self-tapping screws fixed on the sides of the casing. Re-attach them to secure the 4 legs.
These will allow the cover fixing screws to be unscrewed without it falling.
In v e r s i o n o f t h e d r a i n t r a y f o r c o l l e c t i n g o f c o n d e n s a t e s ( K SC R EC O W A T T
®
EF , ER , a n d EC F )
The position of the drain tray for collecting of condensates from the KSCR ECOWATT
®
with cooling or re
-
versible coil is configured at the factory for attachment of the casing to the ground.
For a reverse mounting to the ceiling, it is essential to move the condensate drain tray.
- Disassemble the drawer by unscrewing the four HM8
screws with the wrench 13
- Remove the tray with the cooling coil and the droplet
separator