![ViM KSCR ECOWATT 08 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/vim/kscr-ecowatt-08/kscr-ecowatt-08_insruction-manual_1026846020.webp)
NT00000534-KSCR-ECOWATT-08-18-28-38-52-AN-200625
ENGLISH
20/76
M o d e l
F a n
El e c t r i c a l h e a t e r
M a x i .
s p e e d
( R P M )
F r e q .
( Hz )
V o l t a g e
( V )
P . a b s .
m a x .
( W )
I.
( A )
V o l t a g e
( V )
P . a b s .
m a x .
( W )
No . p i n s a n d
p o w e r
I.
( A )
K SC R 5 2 EI
3 410 50/60
3 Phases
400V + N
1 800
2,8
3 Phases
400V + N
12 000
3x4kW
17,3
K SC R 5 2 EI
3 410 50/60
3 Phases
400V + N
1 800
2,8
3 Phases
400V + N
24 000
6x4kW
34,6
K SC R 5 2 EI
3 410 50/60
3 Phases
400V + N
1 800
2,8
3 Phases
400V + N
36 000
9x4kW
52,0
K SC R 5 2 EI
3 410 50/60
3 Phases
400V + N
1 800
2,8
3 Phases
400V + N
48 000
12x4kW
69,3
K SC R 5 2 EC - ER - EC F
3 410 50/60
3 Phases
400V + N
1 800
2,8
-
-
-
-
M o d e l
C o m p l e t e u n i t
V o l t a g e ( V )
T o t a l P ( k W )
C u r r e n t ( A )
K SC R 0 8 EI M o n o
1 Phase 230 V
7
29
K SC R 0 8 EI T r i
3 Phases 400 V + N
10
15
K SC R 0 8 EC - EF - ER
1 Phase 230 V
0.2
2
K SC R 1 8 EI
3 Phases 400 V + N
16
25
K SC R 1 8 EI
3 Phases 400 V + N
10
16
K SC R 1 8 EC - EF - ER - EC F
1 Phase 230 V
0.4
2
K SC R 2 8 EI
3 Phases 400 V + N
26
40
K SC R 2 8 EI
3 Phases 400 V + N
10
17
K SC R 2 8 EI
3 Phases 400 V + N
17
26
K SC R 2 8 EC - EF - ER - EC F
1 Phase 230 V
1
3
K SC R 3 8 EI
3 Phases 400 V + N
33
47
K SC R 3 8 EI
3 Phases 400 V + N
17
24
K SC R 3 8 EC - EF - ER - EC F
3 Phases 400 V + N
1
2
K SC R 5 2 EI
3 Phases 400 V + N
14
21
K SC R 5 2 EI
3 Phases 400 V + N
26
38
K SC R 5 2 EI
3 Phases 400 V + N
38
55
K SC R 5 2 EI
3 Phases 400 V + N
50
73
K SC R 5 2 EC - ER - EC F
3 Phases 400 V + N
2
3
KSCR ECOWATT
®
EI 08, 6 kW single-phase: Power reducible to 3 kW by removing one 3 kW resistance.
6 . 1 . 2 C O R R l GO C o n t r o l l e r
•
Supply voltage 24 V AC ±15%, 50 to 60 Hz or 21 to 36 Vdc
•
Power consumed models E.W-3: 12 VA, 6 W (DC)
•
Ambient temperature 0...50°C
•
Storage temperature -40...+50°C
•
Max. ambient humidity 90% RH
•
Protection index IP20
•
Connecting plug-in terminals, 4 mm
2
•
Backup of the memory: an integrated long-life battery allows saving long-time settings, real time
included.
El e c t r o m a g n e t i c c o m p a t i b i l i t y d i r e c t i v e ( EM C )
This product meets the requirements of the Directive 2004/108/CE of the European Parliament and
Council (EMC) through compliance with standards EN 61000-6-1 and EN 61000-6-3.
R o HS
This product meets the requirements of the Directive 2011/65/UE of the European Parliament and Council.
In p u t s
Analog inputs for PT1000 sensors (preI- 0.4°C) or 0...10 V DC (preI- 0.15% of the whole
output signal). 12-bit resolution in the A/D signal conversion. Digital Inputs for potential-free contacts.
O u t p u t s
Analog outputs 0...10 V DC, 1 mA, protection against short-circuits. Digital outputs, Mosfet outputs, 24 V
AC/DC, 2 A continuous. Max. 8 A in total.
C o m m u n i c a t i o n p o r t s
1 Web server TCP/IP port, TCP/IP communication,, BACnet/IP.
2 Modbus communication and EXOline RS485 Ports (language REGIN).