It is possible to rename the BACnet ID of the CORRIGO, such as 'CorrigoVentilation' for 'AHU… for ex
-
ample.
All CORRIGOs have the same controller BACnet ID by default, lower figures = 2640.
It is essential to provide different codes when several units are installed on the same network.
By default, the last 4 digits of the CORRIGO serial number can be assigned.
Once this operation is completed, the changes made on E tool with the CORRIGO must be synchronized.
Place the mouse cursor on the left side of the screen and right-click the mouse:
Click on Synchronize Parameters
; any changes made will appear; then click on Modify the CORRIGO,
the Admin code: 1111 will be requested to validate the entry.
After having activated the BACnet, a fixed IP address must be assigned to the unit so that it can integrate
into the network.