5
Installation and Mounting
Adding a Viking Model PRX-3 Medium Range Proximity Card Reader
(1) .74”
diameter
Rear View of the
Optional VE-6x7
Surface Mount Box
3.0”
3.3”
3.0”
2.25”
Condensation
Drain Hole
5.64”
6.72”
3.25”
(2) 0.2 x 0.43 slots
(4) 0.38” diameter
4.5”
2.5”
3/4” Conduit
Knockouts
5.5”
Rough-In Box
(included)
EARTH
GROUND
1
2
AB
C
3
DEF
4
GH
I
5
JKL
6
MN
O
7
PR
S
8
TU
V
9
WX
Y
0
OP
ER
#
Cal
l
VIKI
NG
©
1
2
ABC
3
DEF
4
GH
I
5
JKL
6
MN
O
7
PRS
8
TUV
9
WX
Y
0
OP
ER
#
Mounting Screws: (4) 6-32 X 3/4”
Marine grade 316 stainless steel,
flat head, T-10 Torx security
screws and drive bit (included)
OR
Optional VE-6x7
Surface Mount Box
(not included)
The optional VE-6x7 Surface Mount Box (above) is
designed to be surface mounted to a single gang
box, double gang box, or VE-GNP Gooseneck
Pedestal (shown right). For more information on the
VE-6x7 and VE-GNP, see DOD 424.
K-1700-IP-EWP
shown with VE-6x7
Surface Mount Box
and VE-GNP
Gooseneck Pedestal
(not included)
Peel paper liner and adhere gasket to back of
panel, centering over mounting holes.
Caution:
For rough surfaces (ie: brick, stucco,
etc.) additional caulking may be required.
Earth Ground the
Green/Yellow wire
using the
provided wire nut
Black
Green
White
Black
Green
White
(-) (+)
To Wiegand
Input on
K-1700-IP
Connect to “-/Ground” on Entry System/
Controller and Earth GND
Keep unused leads from shorting
Connect power supply wires to
PRX-3
power
supply wires and negative lead of the controller
*NOTE: Included with PRX-3
*12V DC Adapter
*2200
μ
F
Bi Polar Capacitor
,
(not polarity sensitive)
*3 Position Butt
Connectors
2 Position Butt
Connectors
(included)
To Relay 2
output contacts
on K-1700-IP
COM.
N.O.
White
Violet
When using the
PRX-3
with any Viking Entry System/Controller, the provided 12V DC 500mA power adapter and 2200µF bi polar capacitor should
be used.
When mounting a
PRX-3
in close proximity of the
K-1700-IP
( I.E. using a
PRX-3-MK-GNP
mounting Kit) In programming set “Relay
2 mode” to “Alarm” and wire as shown below. For more Information on
PRX-3
See DOD# 228.
IMPORTANT:
Electronic devices are susceptible to lightning and power station electrical surges from both the AC outlet and the telephone
line. It is recommended that a surge protector be installed to protect against such surges.
K-1700-IP-EWP
shown
with
VE-6x7
,
VE-GNP
pedestal,
PRX-3-MK-
VEGNP
mounting kit
and
PRX-3
Card
Reader