background image

 

LT0186 Issue 2.80 

         27 July 2012 

Page 7 of 10 

SPS Aux

Power

(Note 7)

+24V

0V

B-
B+

NO

COM

+ 24V

ALM -

0 V

Fault

4100ES

T-GEN 50

Master

(Note 2)

NC

EOL 10K

NAC3

 

3.5  T-GEN Wiring with Combined Alarm/Fault Supervision 
 
 
 

F3200

ANCIL

Relay

+ 24V

+24V
0V

0V
0 V

NO

COM

ALM-

NC

SUP

C

NO

NC

S

Relay (Note 4)

+ 24V

0V

- /C

F3200 BELLS

ELD

(See Notes

5 & 6)

+24V
+24V

0V

0V

SIG

NO

COM

SIG

NO

COM

+ 24V

+ 24V

ALM-

0 V

0 V

Fault

Fault

F4000/MX4428

(Note 1)

F3200 Relay Bd

F4000 RRM

(Note 3)

ALM-
0V

+24V

0V

ALM-

T-GEN 50

Master

(Note 2)

T-GEN 50

Slave

(Note 2)

+24V

0V

ALM

 

 

 

 

 
 

 
 
 
 
 
 
 
 
Notes 

1

.  Cut “Ancil Sup link” on F4000, MX4428 Main Board.

 

2.  Fit Lk7 in Relay position to enable Fault Relay. Turn SW4 off. 
3.  RRM must be inside FIP and wired to RESP IN. 
4.  Connect wire from NC term

inal of relay to “S” pin of supervision link. Do not fit Sup link at all.

 

5.  3k3 ELD for MX4428 Ancil Relay and RRM, F3200 Ancil Relay and F3200 Relay Bd. (2k5 (3k3//10k) for F3200 Bells. 
6.  Wire spare pole of AIE switch in series with ELD as per Section 3.1 Figure C if Fault indication required in Isolate. 
7.  The SPS Aux Power output is rated at 2A which is sufficient to power only 1 T-GEN 50 with a maximum speaker load 

of 40W. The 4090-9118 Relay IAM can also be used to control and monitor the T-GEN 50. Please refer to LT0394 or 
LT0350 for further details on using the T-GEN 50 with the 4100ES panel. 

WARNING 

 

If powering a  

T-GEN50 via the 

SPS Aux power 

output the 

speaker load 

must not exceed 

40W 

Содержание T-GEN 50

Страница 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Страница 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Страница 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Страница 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Страница 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Страница 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Страница 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Страница 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Страница 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Страница 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...

Отзывы: